MI 3152(H)
Eurotest
XC (2,5 kV)
Technical specifications
183
12.12
Voltage Drop
ΔU – Voltage drop
Measuring range (%)
Resolution (%)
Accuracy
0.0 ... 99.9
0.1
Consider accuracy of line
impedance measurement(s)*
Uln, Ipsc, Zref, Z
– Line impedance and prospective short-circuit current
technical specification.
Z
REF
measuring range .....................................
0.00 Ω ... 20.0 Ω
Test current (at 230 V) ........................... 6.5 A (10 ms)
Nominal voltage range ........................... 93 V ... 134 V (45 Hz ... 65 Hz)
185 V ... 266 V (45 Hz ... 65 Hz)
321 V ... 485 V (45 Hz ... 65 Hz)
for more information about calculation of voltage drop result.
12.13
Z auto, AUTO TT, AUTO TN, AUTO TN (RCD), AUTO IT
Refer to chapters listed below for detailed technical specification:
– Fault loop impedance and prospective fault current
– Fault loop impedance and prospective fault current in system with RCD
– Line impedance and prospective short-circuit current
– First fault leakage current (MI 3152 only)
and