MI 3152(H)
Eurotest
XC (2,5 kV)
Tests and measurements
126
Measurement procedure
STEP 1:
Measuring the impedance Zref at origin
Enter the
Voltage Drop
function.
Set test parameters / limits.
Connect test cable to the instrument.
Connect test leads to the origin of electrical installation, see
Touch or select the
icon to initiate Zref measurement.
Press the
button to measure Zref.
STEP 2:
Measuring the Voltage drop
Enter the
Voltage Drop
function.
Set test parameters / limits.
Connect test cable to the instrument.
Connect test leads or Plug commander to the tested points,
Start the measurement.
Save results (optional).
Figure 7.50: Example of Zref measurement result (STEP 1)
Figure 7.51: Examples of Voltage drop measurement result (STEP 2)