MI 3152(H)
Eurotest
XC (2,5 kV)
Tests and measurements
138
7.20
Currents
Figure 7.68: Current menu
Measurement parameters / limits
Ch1 clamp type
Current clamp adapter
[A1018, A1019, A1391]
Range
Range for selected current clamp adapter
A1018 [20 A]
A1019 [20 A]
A1391 [40 A, 300 A]
Limit(I1)
Max. PE leakage
[Off, 0.1 mA ... 100 mA]
Connection diagram
Figure 7.69: PE leakage and load current measurements
Measurement procedure
Enter the
Currents
function.
Set parameters / limits.
Connect the current clamp to the instrument.
Connect the clamp to the object under test, see
Start the continuous measurement.
Stop the measurement.
Save results (optional).