MI 3152(H)
Eurotest
XC (2,5 kV)
Tests and measurements
125
7.14
Voltage Drop
The voltage drop is calculated based on the difference of line impedance at connection points
(sockets) and the line impedance at the reference point (usually the impedance at the
switchboard).
Figure 7.48: Voltage drop menu
Measurement parameters / limits
Fuse Type
Selection of fuse type
[Off, gG, NV, B, C, D, K, Custom]
Fuse I
Rated current of selected fuse
Fuse t
Maximum breaking time of selected fuse
I (
U)
1)
Rated current for
U measurement (custom value)
Isc factor
Isc factor
[0.20 ... 3.00]
Test
2)
Test
[Off, L-N, L/L, L1-N, L2-N, L3-N, L1-L2, L1-L3, L2-L3]
Earthing system
Limi
t(ΔU)
Maximum voltage drop
[3.0 % … 9.0 %]
1)
Applicable if Fuse type is set to Off or Custom
2)
With Plug test cable or Plug commander Voltage drop is measured in the same way
regardless of the setting. The parameter is meant for documentation.
Refer to
Fuse tables guide
for detailed information on fuse data.
Connection diagram
Figure 7.49: Voltage drop measurement
– connection of Plug commander and 3-wire test
lead