MI 3152(H)
Eurotest
XC (2,5 kV)
Instrument operation
37
In the Add New window the name and password of the
new user are to be set.
‘Add’ confirms the new user data.
Changes password of the selected user account.
Deletes all user accounts.
Deletes the selected user.
4.6.5 Settings
In this menu different general parameters can be set.
Figure 4.11: Settings menu
Available selection
Description
Touch screen
[ON, OFF]
Enables / disables operation with touch screen.
Keys & touch
sound
[ON, OFF]
Enables / disables sound when touch screen or
key is pressed.
RCD Standard
[EN 61008 / EN 61009,
IEC 60364-4-41 TN/IT,
IEC 60364-4-41 TT,
BS 7671,
AS/NZS 3017]
Used standard for RCD tests. Refer to the end
of this chapter for more information.
Maximum RCD disconnection times differ in
various standards.
The trip-out times defined in individual standards
are listed below.
Isc factor
[0.20 ... 3.00]
Default value: 1.00
Short circuit current Isc in the supply system is
important for selection or verification of