MI 3152(H)
Eurotest
XC (2,5 kV)
Tests and measurements
101
7.6
Continuity – Continuous resistance measurement with
low current
Figure 7.21: Continuity resistance measurement menu
Measurement parameters / limits
Sound
[On*, Off]
Limit(R)
Max. resistance
[Off, 0.1
Ω ... 20.0 Ω]
*Instrument sounds if resistance is lower than the set limit value.
Connection diagrams
Figure 7.22: Tip commander and 3-wire test lead applications
Measurement procedure
Enter the
Continuity
function.
Set test parameters / limits.
Connect test cable to the instrument.