MI 3152(H)
Eurotest
XC (2,5 kV)
Tests and measurements
157
7.29
Z auto - Auto test for fast line and loop testing
Tests / measurements implemented in Z auto test sequence
Voltage
Z line
Voltage Drop
Zs rcd
Uc
Figure 7.96: Z auto menu
Measurement parameters / limits
Protection
Protection type
[TN, TNrcd, TTrcd]
Fuse type
Selection of fuse type
[Off, gG, NV, B, C, D, K, Custom]
Fuse I
Rated current of selected fuse
Fuse t
Maximum breaking time of selected fuse
I (
U)
1)
Rated current for
U measurement (custom value)
Isc factor
Isc factor
[0.20 ... 3.00]
I test
Test current
[Standard, Low]
Type
RCD type
[AC, A, F, B*, B+*,F]
I ΔN
Rated RCD residual current sensitivity
[10 mA, 30 mA, 100 mA, 300 mA,
500 mA, 1000 mA]
Selectivity
Characteristic
[G, S]
Phase
2)
Selection of test
[-, L1, L2, L3]
I test
Test current
[Standard, Low]
Limit(ΔU)
Maximum voltage drop
[3.0 % ... 9.0 %]
Ia(Ipsc (LN),
Ipsc (LPE))
3)
Minimum short circuit current for selected fuse or custom value
Limit Uc
Conventional touch voltage limit
[12 V, 25 V, 50 V]
1)
Applicable if Fuse type is set to Off or Custom.
2)
With Plug test cable or Plug commander Z auto test is measured in the same way
regardless of the setting. The parameter is meant for documentation.
3)
Ipsc (LPE) is considered if Protection is set to TN or TNrcd. Ipsc(LN) is always
considered.
* Model MI 3152 only
Refer to
Fuse tables guide
for detailed information on fuse data.