MI 3152(H)
Eurotest
XC (2,5 kV)
Tests and measurements
123
Measurement procedure
Enter the
Z line m
function.
Set test parameters / limits.
Connect test leads to A 1143
– Euro Z 290 A adapter and switch it on.
Connect A 1143
– Euro Z 290 A adapter to the instrument using RS232-PS/2 cable.
Connect test leads to the object under test, see
Start the measurement using
or
button.
Save results (optional).
Figure 7.47: Examples of high precision Line impedance measurement result
Measurement results / sub-results
Z
Line impedance
Ipsc
Standard prospective short-circuit current
Imax
Maximal prospective short-circuit current
Imin
Minimal prospective short-circuit current
Imax2p
Maximal two-phases prospective short-circuit current
Imin2p
Minimal two-phases prospective short-circuit current
Imax3p
Maximal three-phases prospective short-circuit current
Imin3p
Minimal three-phases prospective short-circuit current
R
Resistance of line impedance
XL
Reactance of line impedance
Uln
Voltage L-N or L-L
Freq
Frequency
Standard prospective short-circuit current I
PSC
is calculated as follows:
𝐼
𝑃𝑆𝐶
=
230 𝑉
𝑍
where
𝑈
𝐿−𝑁
= 230 𝑉 ± 10 %
𝐼
𝑃𝑆𝐶
=
400 𝑉
𝑍
where
𝑈
𝐿−𝐿
= 400 𝑉 ± 10 %