MI 3152(H)
Eurotest
XC (2,5 kV)
Tests and measurements
136
7.19
Harmonics
Figure 7.65: Harmonics menu
Measurement parameters / limits
Ch1 clamp type
Current clamp adapter
[A1018, A1019, A1391]
Range
Range for selected current clamp adapter
A1018 [20 A]
A1019 [20 A]
A1391 [40 A, 300 A]
Limit(THDu)
Max. THD of voltage
[3 % ... 10 %]
Connection diagram
Figure 7.66: Harmonics measurement
Measurement procedure
Enter the
Harmonics
function.
Set parameters / limits.
Connect voltage test leads and current clamp to the instrument.
Connect the voltage test leads and current clamp to the item to be tested, see
Start the continuous measurement.
Stop the measurement.
Save results (optional).