MI 3152(H)
Eurotest
XC (2,5 kV)
Tests and measurements
149
7.25
AUTO TT – Auto test for TT earthing system
Tests / measurements implemented in AUTO TT
Voltage
Z line
Voltage Drop
Zs rcd
RCD Uc
Figure 7.84: AUTO TT menu
Measurement parameters / limits
I ΔN
Rated RCD residual current sensitivity
[10 mA, 30 mA, 100 mA, 300 mA,
500 mA, 1000 mA]
Type
RCD type
[AC, A, F, B*, B+*]
Selectivity
Characteristic
[G, S]
Fuse type
Selection of fuse type
[Off, gG, NV, B, C, D, K, Custom]
Fuse I
Rated current of selected fuse
Fuse t
Maximum breaking time of selected fuse
I (
U)
1)
Rated current for
U measurement (custom value)
Isc factor
Isc factor
[0.20 ... 3.00]
I test
Test current
[Standard, Low]
Limit(ΔU)
Maximum voltage drop
[3.0 % ... 9.0 %]
Limit Uc
Conventional touch voltage limit
[12 V, 25 V, 50 V]
Ia(Ipsc (LN))
Minimum short circuit current for selected fuse or custom value
1)
Applicable if Fuse type is set to Off or Custom.
* Model MI 3152 only.
Refer to
Fuse tables guide
for detailed information on fuse data.