MI 3152(H)
Eurotest
XC (2,5 kV)
Technical specifications
176
12 Technical specifications
12.1
R iso – Insulation resistance
Uiso: 50 V, 100 V
and 250 V
Riso
– Insulation resistance
Measuring range according to EN 61557 is 0.15 M
… 199.9 M
.
Measuring range (M
)
Resolution (M
)
Accuracy
0.00 ... 19.99
0.01
(5 % of r 3 digits)
20.0 ... 99.9
0.1
(10 % of reading)
100.0 ... 199.9
(20 % of reading)
Uiso: 500 V and 1000 V
Riso
– Insulation resistance
Measuring range according to EN 61557 is 0.15 M
… 999 M
.
Measuring range (M
)
Resolution (M
)
Accuracy
0.00 ... 19.99
0.01
(5 % of r 3 digits)
20.0 ... 199.9
0.1
(5 % of reading)
200 ... 999
1
(10 % of reading)
Uiso: 2500V (MI 3152H only)
Riso
– Insulation resistance
Measuring range (
)
Resolution (
)
Accuracy
0.00 M ... 19.99 M
0.01 M
(5 % of r 3 digits)
20.0 M ... 199.9 M
0.1 M
(5 % of reading)
200 M ... 999 M
1 M
(10 % of reading)
1.00 G ... 19.99 G
0.01 G
(10 % of reading)
Um
– Voltage
Measuring range (V)
Resolution (V)
Accuracy
0 ... 2700
1
(3 % of r 3 digits)
Nominal voltages Uiso ............................ 50 V
DC
, 100 V
DC
, 250 V
DC
, 500 V
DC
, 1000 V
DC
,
2500 V
DC
(MI 3152H only)
Open circuit voltage ................................ -0 % / +20 % of nominal voltage
Measuring current ................................... min. 1 mA at R
N
= U
N
1 k
/V
Short circuit current ............................... max. 3 mA
The number of possible tests ................. > 700, with a fully charged battery
Auto discharge after test.
Specified accuracy is valid if 3-wire test lead is used while it is valid up to 100 M
if Tip
commander is used.
Specified accuracy is valid up to 100 M
if relative humidity is > 85 %.
In case the instrument gets moistened, the results could be impaired. In such case, it is
recommended to dry the instrument and accessories for at least 24 hours.
The error in operating conditions could be at most the error for reference conditions (specified in
the manual for each function)
5 % of measured value.