MI 3309 DeltaGT
Appendix C – Pre-programmed autotests (NL)
80
Appendix D – Pre-programmed autotests (NL)
Pre-programmed autotest sequences table
Autotest shortcut
code
01 02 03 04
KL_1_ALG KL_2_ALG KL_1_HEATERS
KL_1_PC
Visual test
Output 200 mA
200 mA
200 mA
Limit
0.30
0.30
0.30
Earth
continuity
Time 5
s
5 s
5 s
Output 500 V
500 V
Limit
1.00 M
0.50 M
Insulation
Time 5
s
5 s
Output
500 V
Limit
2.00 M
Insulation
(probe)
Time
5 s
Output
40 V
Limit
7 mA
Sub. leakage
Time
5 s
Output
Limit
Sub. leakage
(probe)
Time
Output
230 V
Limit
0.50 mA
Differential
leakage
Time
120 s
Output
Limit
Touch
leakage
Time
Functional test
Output 230 V
230 V
230 V
Limit
Power*
Time 10 s
10 s
10 s
Output
Limit
TRMS clamp
current
Time
Polarity test
* optional