MI 3309 DeltaGT
Single test
29
5 Single test
In a Single test mode individual tests can be performed. This is especially helpful for
troubleshooting.
5.1 Performing measurements in single test mode
Select appropriate test in Single test menu.
Figure 5.1: Single test menu
Keys:
/
Selects a single test.
TEST
Enters
Single test measuring menu.
ESC
Returns to
Main menu.
A single test can be started from any Single test measuring menu. Before carrying out a
test the parameters / limits can be edited.
Figure 5.2: Example of single test measuring menu
Keys:
TAB
Selects a parameter.
/
Changes a parameter / limit.
TEST
Starts a single test.
ESC
Returns to
Single test menu.
Note:
Last set parameters will be stored automatically.
Single measurements are stored the same way as autotest results. See chapter
7.1
Saving autotest results
for more information.
5.2 Measurements and inspections
5.2.1 Visual inspection
A thorough visual check must be carried out before each electrical safety test.
The following items should be checked:
Inspection of the device under test for sign of damage.
Inspection of the flexible power supply cable for damage.