MI 3309 DeltaGT
Technical specifications
19
3.5 Differential leakage current
Range Resolution
Accuracy
0.00 mA
19.99 mA
0.01 mA
(5 % of r 5 digits)
Apparent power
Indication only
Powered by....................... mains
Pass levels:....................... 0.25 mA, 0.50 mA, 0.75 mA, 1.00 mA, 1.50 mA, 2.00 mA, 2.25
mA, 2.50 mA, 3.50 mA, 4.00 mA, 4.50 mA, 5.00 mA, 5.50 mA,
6.00 mA, 7.00 mA, 8.00 mA, 9.00 mA, 10.00 mA, 15.00 mA, ----
mA
Test duration:.................... 2 s, 3 s, 5 s, 10 s, 30 s, 60 s, 120 s, --- s
Frequency response: ........ complies with EN61010-1 Figure A1
Test terminals ................... Test socket
Additional error ................. 0,01 mA/A
* Measurement is limited to 120 s if (I
load
> 10 A).
3.6 Touch leakage current
Range Resolution Accuracy
0.00 mA
7.00 mA
0.01 mA
(10 % of r 5 digits)
Apparent power
Indication only
Powered by.....................mains
Pass levels:.....................0.25 mA, 0.50 mA, 0.75 mA, 1.00 mA, 1.50 mA, 2.00 mA 2.25
mA, 2.50 mA, 3.50 mA, --- mA
Test duration:..................2 s, 3 s, 5 s, 10 s, 30 s, 60 s, 120 s, --- s
Frequency response .......complies with EN61010-1 Figure A1
Test terminals .................Test socket – EB/S test probe
* Measurement is limited to 120 s if (I
load
> 10 A).
3.7 PRCD and RCD testing
3.7.1 General RCD Trip-out time
Complete measurement range corresponds to EN 61557-6 requirements.
Maximum measuring times set according to selected reference for RCD testing.
Range Resolution
Accuracy
0 ms
300 ms (½
I
N
)
0.1 ms
0 ms
300 ms (I
N
)
0.1 ms
3 ms
0 ms
40 ms (5
I
N
)
0.1 ms
1 ms