MODIFIED PROCEDURES FOR SPECIAL CONDITIONS
AVTM246004 BITE 2/2P Rev 4 July 2011
51
F
WARNING
Do not remove the BITE 2/2P transmitter current source
leads from the battery until the BITE 2/2P transmitter
current is de-energized. Always disconnect the current
source leads from the battery before removing them
from the J2 connector on the transmitter. Do not leave
the BITE 2/2P connected to the battery when not in use.
5.
Press the Current On/Off switch.
The current is applied to the battery and you can
continue testing.
6.
Test the section.
Repeat the procedure, as needed, depending on the
number of sections in the battery string.
Sectioning a Battery
System with Parallel
Strings
Figure 5-3 shows how to start sectioning a battery system
with parallel strings of cells. To test this string, you must
section the system to supply the proper level of test current
needed to stimulate the cell impedance or strap resistance
measurements.
You may see other ripple current influences as noted in the
single string of cells (see Figure 5-1) and you may have to
interchange the polarity of the current source lead clips.
F
WARNING
Do not remove the current source leads from the battery
until the transmitter is turned off. Always remove the
leads at the battery connection before removing them
from the J2 connection on the transmitter.