AVTM246004 BITE 2/2P Rev 4 July 2011
40
If you do not want to test the
strap, pull the trigger and go
directly to Step Eight.
The
receiver
LCD now displays the word STRAP, which
prompts you to test the strap that is associated with the
cell you just tested.
CELL
VOLTS
m
Ω
001
13.43
23.33
T01
STRAP
0.112
4.
Position the
receiver
and potential probe on top of the
battery strap terminals, and then press the probes down.
See the sample placement shown in Figure 4-7.
Red
Black
Current Source
Lead from
Transmitter
connected to
terminal positive
plate
Current Source
Lead from
Transmitter
connected to
terminal negative
plate
Figure 4-7: Receiver and potential probe positioned
on top of battery strap terminals