67
By the
CIDUNCACK
parameter you can
enable
that the
Easy 2
will send immediate and
automatic acknowledge to the alarm center
–
independently that the signalling to the centre
was sent successfully or not.
This could be important for some alar, centers where the handshake for alarm signalling is
not imporant or not available. When the surveillance centre is not able to send a response
acknowledge to an incoming alarm event, this can be helpful to apply.
You can use this feature only for your own risk!
The
STARTUPCID
parameter allows the immediate status sending and signalling when the
device starting up. When it is
enabled
, then in case of a restart or turning off the
Easy2
will
automatically sends the restart status (e.g. CID code: E901
–
Restart (by software), or CID
code: E900
–
Turning on (by hardware)).
By the
REBOOTDAY
parameter you can
enable
the industrial- and safety standard daily
once device restart event.
The
ROAMING
feature
enables
the roaming operation on the mobile network, which is
necessary to be also supported by the mobile operator of the SIM card. When you are
attempted to use the roaming, then you have to fill the value country code prefixes (e.g. the
+49 prefix for Germany in case of national usage or the 0049 prefix usage in case of