background image

Operation

43

Subject to technical changes.
200114

BA-42820-02-V03

Water sampling station 

EASYPRO

  

Operating instructions

7.  Time:

 Configure the timer to the desired duration.

8.  “Off” or “Active”: 

It will be displayed here whether the timer is cur-

rently active. If this is the case, the display will show how long it is still 
active.

9.  “Start” and “Stop” button:

 The timer can be started or stopped 

manually, e. g. for a shock chlorination.

ü 

Configuration completed.

Configure switching via ECO control

A limit value control is defined for the "Economy mode”. The limit value 
control is generally used to reduce the circulation capacity.

If the measured values are located within the setpoints, the output is 
closed. If the digital input is also switched for switching to another refer-
ence set, “Economy mode” is active and the switch will be made to the 
desired reference set.

Pre-conditions for actions:

ü 

The limit value control is configured as described in section „Limit 
value control“ on page 33.

To configure, working in the “Setpoints” menu item, select the “Switch-
ing” tab. 

Perform the following work steps:

1.  Automatically switching the reference sets:

 Set a checkmark 

here.

2.  Switch-over: 

Select “Switching input”.

3.  Function: 

Select “ECO control”.

4.  Reference set:

 Select the reference set to which is to be switched.

5.  Digital input: 

The digital input in use is indicated here.

ü 

Configuration "Switchover via ECO control” completed.

9.6.3.2  Switching via timer

Up to ten timers can be configured parallel to the switching via a digital 
switching input (see section 9.6.3.1 „Switching via digital inputs“ on page 
42). Times are defined for the point at which the timers should switch 
to a certain reference set.

To configure, working in the “Setpoints” menu item, select the “Switch-
ing” tab.

Perform the following work steps:

1.  Automatically switching the reference sets: 

Set a checkmark 

here.

2.  Switch-over: 

Configure up to ten timer switches and state the fol-

lowing information.

3.  Off/Active:

 Switch on the timer.

4.  Time:

 Configure a time at which the switch-over is to be made. State 

the hour and minutes.

5.  Monday – Sunday: 

Set a checkmark against every weekday on 

which the timer should be active.

6.  Reference set: 

Select the reference set to which is to be switched.

ü 

Configuration "Switchover via timer” completed.

9.7  Access via network

Accessing the device via a network requires that it is connected to an ex-
isting Ethernet or RS485 network.

Further information about connection to an existing network is specified 
in sections 7.11 „Connecting Ethernet“ on page 26, 7.12 „RS485 inter-
face“ on page 26 and 8.5 „Network settings“ on page 35.

i

If connection problems are experienced during access via net-
work, check the configuration of your security software.

Modbus

You can access certain data on the device via the Modubus protocol using 
both Ethernet and the RS485. You need the Modbus protocol e.g. For the 
connection with a control panel or a PLC. Modbus TCP/IP is supported for 
Ethernet and Modbus RTU is supported for the RS485 interface.

The Modbus addresses of your device are stated in section 13 „Modbus 
addresses“ on page 51.

Web browser (only Ethernet)

You can access the device data using all network devices which are fitted 
with a web browser. You will require the IP address, subnetmask and pos-
sibly the MAC address of the device.

The network settings of your device are listed under Main menu > System 
> Service > Network.

Open the web browser of your end device and enter the IP address of the 
device in the address row. The page of the device will open and provide a 
range of information.

TFTP protocol (only Ethernet)

You can access the device memory via a TFTP client software as long as 
TFTP is activated in the network settings. You need the device IP address 
for access.

i

The network settings of your device are listed under Main 
menu > System > Service > Network.

Summary of Contents for Jesco EASYPRO

Page 1: ...ontrol Liquids Gases Systems Lutz Jesco GmbH 2020 BA 42820 02 V03 Water sampling station EASYPRO Operating instructions Read the operating manual The user is responsible for installation and operation...

Page 2: ......

Page 3: ...3 4 MC C MD C MP C MK C 18 6 3 Water sampling station EASYPRO 1 1 2 2 MBB C MEE C 19 7 Installation 20 7 1 Installation location of the water sampling station EASYPRO 20 7 2 Wall mounting 20 7 3 Insta...

Page 4: ...ers to a potentially hazardous situation Failure to follow this instruction may lead to death or se vere injuries CAUTION Refers to a potentially hazardous situation Failure to follow this instruction...

Page 5: ...n Failure of required maintenance and repair methods n Risk to persons when working on the device n Danger to the environment from overdosing 2 3 Working in a safety conscious manner Besides the safe...

Page 6: ...ntion 2 4 3 Trained persons Trained persons have received training from the operator about the tasks they are to perform and about the dangers stemming from improper be haviour Trained persons have at...

Page 7: ...applications and can be deployed universally Its main application is to maintain the quality of water by evaluating the measurements of chlorine value pH value and Redox value as well as conductivity...

Page 8: ...Buffer solutions for adjusting each measuring cell The measuring cells are packaged separately and not pre installed 4 2 Design and function The water sampling station can continuously measure the lev...

Page 9: ...function here external stop 3 Parameter calculated here effective chlorine 4 Module for pH and Redox single rod measuring cells Control system 1 Controller 1 2 Controller 2 1 Controlling the free chlo...

Page 10: ...e g conductivity measuring cell 11 buffer solutions 12 Outflow tap Tab 5 Position numbers water sampling station EASYPRO 4 4 3 1 Main view The main menu view will appear upon the start of the product...

Page 11: ...P N S N 42820005 2 1 3 6 4 5 EASYPRO Fig 5 Rating plate water sampling station EASYPRO No Position 1 Product name 2 Technical specification 3 WEEE label 4 Serial number 5 Part number 6 Month year of m...

Page 12: ...nding on version Number of measuring inputs 2 3 4 3 2 x 2 Free chlorine Amperometric 3 electrode measuring cell with potentiostat DMZ3 1 mg l 0 15 dependant on the meas uring cell transcon ductance 0...

Page 13: ...Amperometric 3 electrode measuring cell with potentiostat DMZ3 1 mg l 0 15 dependant on the measuring cell transconduct ance 2 x 0 15 dependant on the measuring cell transconductance CS120 excess chlo...

Page 14: ...e with KCI gel filling Counter electrode Precious metal Copper Silver Measuring range 0 15 mg l Cl2 0 20 mg l Cl2 0 20 mg l Cl2 Transfer slope 20 30 A mg l Electrolyte Sample water Electrical connecti...

Page 15: ...asuring total chlorine Measuring cell GCM GCM GCM Measuring input Total chlorine Measuring range 0 2 mg l Clges 0 5 mg l Clges 0 10 mg l Clges Transfer slope 4 20 mA Electrolyte Diaphragm cap with ele...

Page 16: ...5 dependant on the measuring cell transconductance CS120 excess chlorine measuring cell mg l 0 10 dependant on the measuring cell transconductance Diaphragm covered measuring cell mg l 0 10 dependant...

Page 17: ...output e g for solenoid valve n Depending on the control deviation and the defined control parameters the relay pulls in or drops out for the set cycle duration If the cycle lasts 30 seconds and the c...

Page 18: ...sampling station EASYPRO 3 4 MC C MD C MP C MK C All dimensions in mm Fig 8 Dimensions water sampling stations EASYPRO 3 4 MC C MD C MP C MK C 500 42820001_5 Ma bild Messwassertafel EASYPRO 2 mit Abde...

Page 19: ...changes 200114 BA 42820 02 V03 Water sampling station EASYPRO Operating instructions 6 3 Water sampling station EASYPRO 1 1 2 2 MBB C MEE C 10 117 874 900 200 490 464 Fig 11 Dimensions water sampling...

Page 20: ...station PLEASE NOTE Hydraulic distortion of the measurement results Incorrectinstallationofthehydrauliclinescandistortthemeasurement results As a result the controlling of connected systems and contr...

Page 21: ...is available The voltage supply is deactivated before the start and secured against reactivation The housing is open Resources required Schuko plug Wire end sleeves 0 75 2 5 mm DANGER Mortal danger f...

Page 22: ...utput 3 green 7 LED output 4 red 8 LED output 4 green 9 10 LED output GND Ground for the LEDs 11 Disturbance variable input 0 4 20 mA 12 13 Analogue output 1 0 4 20 mA working resistance max 500 14 15...

Page 23: ...nic distortion of the measurement results Incorrect installation of the electrical cables can distort the measure mentresults Asaresult thecontrolofconnecteddevicescanbefaulty Do not route the connect...

Page 24: ...1 black BK 2 Temperature input blue BU 3 Conductivity measurement input brown BN 4 Conductivity measurement input white WH Tab 25 Terminal connection of the conductive input circuit board to the condu...

Page 25: ...20 mA The output connects a servomotor with or without feedback 3 2 1 Fig 24 Output circuit board with servomotor 20 mA Terminal Function Description 1 GND 2 Input feedback 4 20 mA 3 Output 4 20 mA T...

Page 26: ...parallel to the inductive load 3 Should it prove impossible to perform point 2 clamp the interference suppression element parallel to the relay output RC protection for relay connected 7 11 Connectin...

Page 27: ...ivity The connecting cables are already installed on the TOPAX MC controller and need only be connected to the measuring cells Pre conditions for actions The installation of the water sampling station...

Page 28: ...arameters n With a control output power of Y 25 and a maximum pulse frequency of 100 pulses min the controller would output 25 pulses min x Pulse length 2 sides pulse length n 0 3600 seconds cycle dur...

Page 29: ...or a timer Set the centre row of the control function Tab 18 Multi channel controller TOPAX MC measuring inputs on page 16 and press the right hand arrow Controllers 1 to 4 must be assigned to the out...

Page 30: ...e calculation Example If the factor 2 and the disturbance variable amounts to 42 the controller can be set to a maximum of the control variable Y 84 If the factor 0 5 and the disturbance variable amou...

Page 31: ...surement has a higher effective chlo rine content than is actually in the process water For high pH values sig nificant differences will therefore occur between the expected and actual disinfection if...

Page 32: ...ntroller tab 2 Working in the Controller tab configure the controller output and state the following information 3 Y alarm Activate the Y alarm The Y alarm is a safety cut out If the controller output...

Page 33: ...steps 1 In the main menu under System Outputs navigate to the Digital tab 2 Working under Digital output select the desired output 4 The free outputs will be displayed which you have configured as an...

Page 34: ...Ds Perform the following work steps 1 Working in the main menu under System Outputs navigate to the External LEDs tab 2 Working under LED select the desired LED 3 Configure the LED by entering the fol...

Page 35: ...puts and outputs and the adjust ment of the sensors are accessible here This level is required for de vice configuration and should only be operated by experienced users n 3 Level The service menu is...

Page 36: ...book i You can open and analyse CSV files with a suitable programme e g MS Excel You can also view all CSV files on the device 9 2 1 View and open files You can display the logbook files on the device...

Page 37: ...ells 1 and 3 for the left hand area Select measuring cells 2 and 4 for the right hand area Fig 32 View of the EASYPRO water sampling station as a double version 9 5 2 pH single rod measuring cell Cali...

Page 38: ...the entry with the green checkmark 1 point adjustment of the pH value completed 9 5 2 3 Offset compensation External influences can cause the pH value measured with the photome ter to deviate from th...

Page 39: ...y present The sensor is operated with sample water Perform the following work steps 1 Working in the main menu under Calibration navigate to the Sen sors tab 2 Working under Sensor select the sensor t...

Page 40: ...in the main menu under Calibration navigate to the Sen sors tab 2 Working under Sensor select the sensor that measures the con ductivity and which you wish to calibrate 3 Press the 1 points button 4...

Page 41: ...servomotor is switched on and has been connected properly The output has been configured correctly see Tab 20 Functions of the individual controllers on page 17 Perform the following work steps 1 Work...

Page 42: ...points menu item navigate to the Switching tab Set a checkmark against Switch setpoints automatically 2 Working in the Manual mode menu set a checkmark against Switch setpoints automatically You can u...

Page 43: ...he reference sets Set a checkmark here 2 Switch over Configure up to ten timer switches and state the fol lowing information 3 Off Active Switch on the timer 4 Time Configure a time at which the switc...

Page 44: ...ling station EASYPRO 4 on page 10 pos 3 as well as the outgoing hose connection from the outflow tap Fig 2 Water sampling station EASYPRO 4 on page 10 pos 12 and the measuring cell valve 5 Unscrew the...

Page 45: ...roller Tab 41 Maintenance intervals 11 2 Finishing maintenance Perform the following work steps 1 Make a note of the date and scope of the maintenance performed 2 In the Service menu navigate to the S...

Page 46: ...ow controller and open carefully 4 Replace all the O rings in the flow controller Lightly grease all the new O rings with silicone grease before insertion 5 Replace the diaphragm 6 Check all further c...

Page 47: ...2 Using the socket wrench unscrew the retaining nuts from the white protective plate and remove the plate 3 Using the socket wrench unscrew the two nuts from the input circuit boards which you need to...

Page 48: ...factory set configuration file unchanged and save your personal configuration in a new file Given problems with the configuration this enables you to return to a functioning configuration quickly Per...

Page 49: ...ample water inflow is soiled Check the visible parts and filter Fig 2 Water sampling station EASYPRO 4 on page 10 pos 3 for soiling and clean if necessary The LEDs are continually red The controller d...

Page 50: ...and use other chemicals for disinfection The TOPAX MC controller loses all settings after he has been disconnected from the network and then recon nected The battery is empty n Check that the battery...

Page 51: ...ss 2002 0x3536 transferred 2003 x Status of digital inputs Displays the terminal logic not the configured software function The individual bits are assigned directly to the input clamps Example 0x01 m...

Page 52: ...5 No type 2021 2022 x Measurement Number of positions after the decimal point see unit 4 bytes signed int 2023 x Unit Number Unit decimal places 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 mA A ppm mg l S cm m...

Page 53: ...x x Minimum and maximum alarm Write 0 clear alarm Read Bit 0 minimum alarm is active Bit 1 maximum alarm is active 2035 x x Y alarm Write 0 clear alarm Read Bit 0 Y alarm is inactive Bit 1 Y alarm is...

Page 54: ...ual mode 2107 2108 x x Setpoint 1 Number of positions after the decimal point see unit 4 bytes signed int 2109 2110 x x Setpoint 2 If 2 side control is active 4 byte signed int 2111 x x Xp Number of p...

Page 55: ...um alarm Sensor 1 minimum alarm Sensor 2 minimum alarm Sensor 3 minimum alarm Sensor 4 minimum alarm 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2226 x Alarm status 2 If the bit is set the associated alarm...

Page 56: ...put 7 Digital input 8 Sensor 1 calibration not OK Sensor 2 calibration not OK Sensor 3 calibration not OK Sensor 4 calibration not OK Temperature 1 calibration not OK Temperature 2 calibration not OK...

Page 57: ...manufactured in accordance with valid good engineering practice In accordance with article 4 section 3 as a pressure device the EASYPRO does not carry CE marking and cannot be issued with a EU dec lar...

Page 58: ...requisitos sanitarios y de seguridad vigentes de las directivas de la U E citadas a continuaci n Esta declaraci n ser invalidad por cambios en el aparato realizados sin nuestro consentimiento 2014 30...

Page 59: ...es No Properties Corrosive Yes No We hereby certify that the product has been cleaned thoroughly inside and outside before returning that it is free from hazardous material i e chemical biological tox...

Page 60: ...one Date Address Contact person Manufacturer order no Date of delivery Device type Serial number Nominal capacity nominal pressure Description of fault Service conditions of the device Point of use sy...

Page 61: ...ional range Xp The proportional range Xp p proportion of a P PI or PID controller indi cates the amount by which the actual value X must deviate from the setpoint W so that the variable Y 100 If the c...

Page 62: ...value control 33 Logbook 37 Long term shut down 45 M Maintenance 46 Measuring cells 14 Open 3 electrode measuring cell 14 N Notes for the Reader 4 O Operation 37 P Personnel qualification 5 Personnel...

Page 63: ......

Page 64: ...Copyright 2020 by Lutz Jesco GmbH Lutz Jesco GmbH Am Bostelberge 19 D 30900 Wedemark Phone 49 5130 5802 0 info lutz jesco com www lutz jesco com Operating instructions Water sampling station EASYPRO...

Reviews: