a. Remove the top cover. See
“Remove the top cover” on page 132
b. Remove the power supply unit. See
“Remove a hot-swap power supply unit” on page 105
c. Disconnect the flash power module cable from the RAID adapter. See
.
d. Remove the flash power module. See
“Remove the flash power module” on page 78
Step 2. Remove the two screws.
Figure 94. Cover screw removal
Step 3. Carefully slide the power distribution board cover forward and lift it out of the server.
Figure 95. Power distribution board cover removal
Step 4. Disconnect the cables from the power distribution board. See
“Hot-swap power supply unit cable
.
110
ThinkSystem SR250 V2 Maintenance Manual