PRO1 Sentry Switched DC PDU
133 of 211
Restart Options for the Sentry DC PDU:
Note: About Unit Persistence:
The PRO1 products support unit persistence. This means that if a link unit is connected to a master unit, and
the
link unit is disconnected (powered down or accidentally disconnected), and the master unit is restarted, the link
unit will be reported as “Not Found” after the restart because the link unit is no longer physically conne
cted to the
master.
However, the association between the master/link units is retained to allow the continuation of alerts. If the
disconnected link unit is physically re-
connected to the master, the “Not Found” status will return to “Normal”
status.
To intentionally remove a link unit from connection with a master unit, the link unit must be purged using the
Purge function.
Unit persistence affects
all
connected
master/link units
whether or not they are connected in a multi-linking
configuration.
This res
tart option …
performs this action on the PRO1 …
Restart
Performs a warm boot; system user/outlet/outlet group configuration settings and outlet
states are
not
changed or reset with the
restart
command.
Restart and reset to factory
defaults
Resets the non-volatile RAM where configuration values are stored. This option clears all
administrator-editabled fields and resets all CLI configurable options to their factory
default values, including all user accounts.
Resetting the PDU to factory default values also resets all TCP/IP and Telnet/Web
configurations. Reconfiguring TCIP/IP and Telnet/Web settings is required.
Restart and reset to factory
defaults, except network
Same action as “Restart and reset to factory defaults” described directly above, but
network protocol settings are
not
changed.
Restart and download
firmware via FTP
New versions of firmware can be uploaded using FTP. To begin an FTP upload session,
you must first configure the FTP host address, username/password, filename, and file
path.
When initiating an FTP upload session, the PDU restarts and uploads the firmware file
specified with the FTP filename command from the previously configured FTP host.
Restart and generate a new
X.509 certificate
Generates a new X.509 certificate issued and signed by a certificate-authority.
Restart and compute new
SSH keys
Generates new private and public SSH keys with the proper location and permisssion.
Summary of Contents for 48DCWC-04-2X100-D0NB
Page 1: ......
Page 2: ...Sentry Switched DC PDU 2 of 211...
Page 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Page 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Page 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Page 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Page 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Page 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Page 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...