Sentry Switched DC PDU
31 of 211
Star Linking Technology
Server Technology’s
Sentry DC product line provides Star Linking technology that supports the optional
linking of up to three expansion (link) units per one master unit, allowing a single IP address for multiple
cabinets.
Note:
The Star Linking feature is available with PRO1 Sentry Switched DC PDUs and the PRO1/PRO2 AC
PDUs.
The following illustrations (using PRO1/PRO2 PDUs in this example) show multi-linking between separate
units and within the cabinet:
Multi-Linked PDUs Multi-Linking View in the Equipment Cabinet
Redundant Power and Communication
The Star Linking arrangement is fault tolerant, with redundant power coming from the first link unit.
The arrangement also offers significant cost reduction as the link units do not require a network card.
Another significant advantage of Star Linking technology is that if power in the master unit is lost,
communication will continue with the other link units, which is a major improvement over a daisy-chain
linking configuration.
Outlet Grouping
The multi-link arrangement allows outlet grouping across the master and three link units.
Cable Length
The maximum cable length allowed from link unit to master unit is 21-feet (6.4 meters).
Summary of Contents for 48DCWC-04-2X100-D0NB
Page 1: ......
Page 2: ...Sentry Switched DC PDU 2 of 211...
Page 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Page 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Page 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Page 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Page 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Page 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Page 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...