PRO1 Sentry Switched DC PDU
109 of 211
To Configure the SNMP Trap:
1.
Format: Configures the SNMP trap format version. The trap format can be SNMP v1, v2c, or v3. The
default is v1, regardless of the versions that are enabled for the agent.
2.
v2 Community: SNMP trap community for the PDU.
3.
v3 Username: (Optional). Provide a trap username to display on SNMP v3 activity logs to identify user
actions. The trap username can be 1-31 alphanumeric characters; spaces are allowed; the name is case
sensitive.
4.
For Destination 1 and Destination 2: Provide first and second trap destinations as a hostname or IP
address.
5.
Error Repeat Time: Sets the SNMP trap repeat time for an object in an event condition. Provide a time
value from 1 to 65535 (in seconds).
6.
IP Restrictions: From the drop-down menu, select None (default) or Trap Destinations Only. If Trap
Destinations Only is selected, SNMP Manager GET and SET requests are allowed only from the IP address
of the defined trap destinations.
7.
System Name/Location/Contact: (Optional) Type the system name, location, and contact string from 1-63
characters.
8.
Click
Apply
.
To
Configure the
SNMPv3 Agent:
1.
Check (or uncheck) the Enable checkbox to enable/disable SNMP v3 Agent support.
2.
Engine ID: Unique system-assigned ID for each PRO1 DC PDU that cannot be user-edited.
3.
Click the SNMPv3 User Configuration link at the bottom of the
Network > SNMP
page. The following user
configuration page displays to allow you to add (or edit/delete) an SNMPv3 user.
Summary of Contents for 48DCWC-04-2X100-D0NB
Page 1: ......
Page 2: ...Sentry Switched DC PDU 2 of 211...
Page 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Page 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Page 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Page 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Page 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Page 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Page 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...