PRO1 Sentry Switched DC PDU
43 of 211
Network-Enabled Modes
Descriptions for the network-enabled modes:
•
Network disabled
–
No IPv4 or IPv6 addresses available.
•
IPv4 only, DHCP disabled (static IPv4)
–
If the IPv4 Static Address and Net Mask of the PDU are valid, they
will be set.
•
IPv4 only, DHCP enabled (DHCP IPv4)
–
The PDU will try to resolve an IPv4 DHCP address. If a DHCP
address cannot be obtained after 90 seconds, the PDU can: (1) optionally fall back to its static IPv4
settings, or (2) indefinitely wait to acquire an address based on DHCP configuration settings
. This setting
is the default.
•
Dual IPv6/IPv4, DHCP disabled (static IPv6/IPv4)
–
If the IPv6 Static Address and prefix of the PDU are
valid, they will be set. Otherwise, the PDU will attempt to use DHCPv6 to obtain an IPv6 address. In
addition, if the IPv4 Static Address and Net Mask of the PDU are valid, they will be set.
•
Dual IPv6/IPv4, DHCP enabled (DHCP IPv6/IPv4)
–
The PDU will try to resolve both its IPv6 and IPv4
addresses by DHCP. If both DHCP requests are answered, the
primary
DNS server of the PDU will become
the
primary
IPv6 DNS server, and the
secondary
DNS server of the PDU will become the
primary
IPv4 DNS
server. If only one of the DHCP requests is answered, the DNS servers of the PDU will map to the
primary
and
secondary
DNS server from that request. If a DHCP address cannot be obtained after 90 seconds, the
PDU can: (1) optionally fall back to its static IPv4 and/or IPv6 settings, or (2) indefinitely wait to acquire an
address based on DHCP configuration settings.
Notes:
•
For all network-enabled modes described above, the PDU will set an auto-configured IPv6 address, and if
IPv6 router announcements are active, a stateless DHCP IPv6 address will also be set. Further, in all
network-enabled modes, at least one IPv4
or
one IPv6 address will be active.
•
For maximum backw
ard compatibility, the default network mode is “IPv4 only”.
Summary of Contents for 48DCWC-04-2X100-D0NB
Page 1: ......
Page 2: ...Sentry Switched DC PDU 2 of 211...
Page 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Page 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Page 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Page 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Page 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Page 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Page 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...