PRO1 Sentry Switched DC PDU
106 of 211
About RADIUS Vendor-Specific Attributes (VSA)
In addition to the protocol-required attributes, the RADIUS authentication process can be extended by using
private vendor-specific attributes (VSA). This extension allows Server Technology to create its own proprietary
attributes to support features and services using the PRO1 PDU in the RADIUS authentication process.
Server Technology has defined and formatted RADIUS vendor-specific attributes (VSA) in the dictionary.sti file,
which is available from Server Technology. The PDU is configured to recognize and use the configuration values in
the file as specified by the network administrator, indicating to the RADIUS server that the defined attributes are
based on Server Technology’s unique enterprise
vendor code.
Using the format of the dictionary.sti file (located on the Server Technology FTP site at
), the
PRO1 RADIUS implementation supports the following vendor-specific attributes:
Vendor-Specific Attribute (VSA) Descriptions
Attribute
Description
STI-Access-Level
Indicates user access level for the Switched PRO1; values are 1-6 as follows; a valid access level is required or access
to the unit is denied.
Valid Access Levels:
1 = Admin
2 = Power User
3 = User
4 = Reboot Only
5 = On Only
6 = View Only
STI-Env-Mon
Determines user access rights to environmental monitoring; values are Yes or No. For the STI-Access-Level value
other than 1 (Admn), if STI-Env-Mon is not included for a user, default is no.
STI-Outlets
Specifies user access rights to outlets; values are space-delimited strings of absolute IDs, names, or the special
keyword “ALL”. String values are case-sensitive and limited to 253 characters. This attribute can be repeated to
append strings that declare additional access rights. For STI-Access Level values other than 1 (Admn) and 2 (Power
User), if STI-Outlets is not included for a user, the default is no outlet.
STI-Groups
Specifies user access rights to groups of outlets; values are space-delimited strings of absolute IDs, names, or the
special keyword “ALL”. String values are case-sensitive and limited to 253 characters. This attribute can be repeated to
append strings that declare additional access rights. For STI-Access Level values other than 1 (Admn) and 2 (Power
User), if STI-Groups is not included for a user, the default is no group.
STI-Ports
Specifies user access rights to ports; values are space-delimited strings of absolute IDs, names, or the special
keywo
rd “ALL”. String values are case-sensitive and limited to 253 characters. This attribute can be repeated to
append strings that declare additional access rights. For STI-Access Level values other than 1 (Admn) and 2 (Power
User), if STI-Ports is not included for a user, the default is no ports.
Note:
User access levels must be configured using the
dictionary.sti
file. If the administrator does not use the
dictionary.sti
file to configure a user, the user will not have access rights to the PDU.
Summary of Contents for 48DCWC-04-2X100-D0NB
Page 1: ......
Page 2: ...Sentry Switched DC PDU 2 of 211...
Page 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Page 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Page 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Page 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Page 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Page 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Page 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...