PRO1 Sentry Switched DC PDU
54 of 211
Monitoring > Cords
The
Cords
page displays cord hardware and operational information for inlet type, power capacity (W), state, and
status.
Note:
The inlet type was determined for the product at factory assembly and cannot be user-edited.
What to look for:
The cord power graphs display a blinking warning (yellow) when the total input load exceeds the user-defined
threshold. If an overload occurs, a blinking error condition (red) is displayed. The unit continues to display yellow
and red states until the condition changes or the issue has been resolved.
The default input feed high load threshold is 80% of the input feed maximum load capacity.
Cord power thresholds are user-defined
at Configuration > System > Cords
.