PRO1 Sentry Switched DC PDU
173 of 211
Parameters
The
set outlet
command uses the following sub-parameters:
script delay
Sets the time to wait after the script has executed to outlet state change. 1-
15 seconds.
shutdown delay
Sets the time to wait after the shutdown notification to host before outlet
state change. Valid range is 1-900 seconds.
on
Sets outlet to sequence on after system boot.
off
Sets outlet to remain off after system boot.
last
Sets outlet to match its last state prior to system boot after system boot.
alarmhi
Sets high alarm value.
alarmlo
Sets low alarm value.
warnhi
Sets high warning value.
warnlo
Sets low warning value.
min <= alarmlo <= warnlo <= warnhi <= alarmhi <= max
Command Access
Admin level only