PRO1 Sentry Switched DC PDU
121 of 211
Access (Managing Users)
The
Access
section of the Web interface determines how a PRO1 PDU user works with the network and system by
configuring the options related to a user: authentication, privilege levels, user access to the unit, and additional
functions for individual local users and user groups.
Note:
The
Access
section only allows the administrator to determine how the user will access and use the
network and system. To set up network protocol parameters, see the
Network
section.
Access > General
The
General
page allows configuration of local and remote access settings.
To configure general system access:
Access Method: From the drop-down menu, select an option to enable one of several authentication methods to
control user access to the PDU. Only one method can be enabled at a time: Local Only (default), LDAP Only, LDAP
Then Local, RADIUS Only, RADIUS Then Local, Only, Then Local.
Button Configuration Reset:
Check (or uncheck) the Enable checkbox to enable (or disable) physical access to the
Reset
button on the PRO1 hardware.
The PDU is designed with a reset button on the hardware unit that can be used when a forgotten firmware
password prevents logging into the unit. The reset button sets all configuration values back to factory default
settings, allowing the administrator to retrieve the admn/admn default administrator login.
To access the button on the unit, you need a non-conductive metallic tool that fits inside the recess. If you press
and hold the
Reset
button on the unit for more than 15 seconds, the reset action will terminate.
Note:
This method of physical access to the unit will not work if the reset button has already been disabled by the
administrator through the firmware GUI at
Configuration > Access > General > Button Configuration Reset
(show
in the screen example above) or through the firmware CLI with the
set access button
[
enabled/disabled]
command. For security, the administrator can choose to disable the button through firmware to inhiibit a user
from causing a reset on the unit.
Summary of Contents for 48DCWC-04-2X100-D0NB
Page 1: ......
Page 2: ...Sentry Switched DC PDU 2 of 211...
Page 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Page 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Page 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Page 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Page 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Page 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Page 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...