PRO1 Sentry Switched DC PDU
119 of 211
Network > ZTP
The Network > ZTP page provides the settings for using the optional Zero Touch Provisioning (ZTP) feature. ZTP
allows PDUs to be provisioned and configured automatically during the initial bootup, or whenever needed, to
automate network setup, user permission updates, and other PDU modifications as necessary.
About Automatic Provisioning:
Automatic and continuous provisioning means you can revise the ZTP configuration file (config.ini) as needed and
push the file down through the ZTP process multiple times. ZTP will recognize the latest revisions in the
configuration file, giving you the flexibility of a ZTP process for maintenance as well as for initial provisioning.
Note:
For more information about ZTP and the automatic provisioning methodology used with PRO1 products,
see the Server Technology website
for Technical Note: 303-9999-44,
“Zero Touch Provisioning”.
Resetting ZTP:
Reset is available only when ZTP is enabled. When reset to “Not Provisioned”, the PDU will attempt ZTP again
after the next RESTART, behaving as it did prior to being provisioned.
After a PDU has been successfully provisioned by ZTP, to use the GUI to reset ZTP to re-provision the PDU again
either after the next RESTART or next DHCP lease renewal, click the
Reset
button on the ZTP window.
Note that the PDU’s provisioned state (“Provisioned” or, “Not Provisioned”) is not reset by disabling ZTP. When
ZTP is re-enabled on a previously provisioned PDU, the state will still show as provisioned.
Summary of Contents for 48DCWC-04-2X100-D0NB
Page 1: ......
Page 2: ...Sentry Switched DC PDU 2 of 211...
Page 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Page 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Page 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Page 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Page 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Page 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Page 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...