PRO1 Sentry Switched DC PDU
57 of 211
Monitoring > Outlets
The
Outlets
page lists the outlets in the DC PDU with a quick overview of general outlet information, including
operational status based on user-configured thresholds for current, active power, and power factor.
Also displayed are the last user action (on, off, reboot) issued on the outlet (shown in the State column), and the
outlet’s last reported condition (shown in the Control State column).
The page allows a fast drill-down from the ID link for more operational data about a specific outlet in the list.
What to look for:
The operating status of all outlets should be Normal. If necessary, view operational details for an outlet. The ID
and socket type are determined at factory assembly and cannot be user-configured.
Each outlet has a unique number, and
the numbering sequence of outlets is not associated with the unit’s branch
or phase number. For example, a 30-outlet PDU unit will have outlet numbers sequenced from 1 to 30.
The outlet status displays a blinking warning (yellow) and red (error condition) when an outlet exceeds the user-
defined thresholds. The status continues to display yellow and red states until the condition changes or the issue
has been resolved.
A descriptive text outlet name can be configured at
Configuration > System > Outlets
.
Summary of Contents for 48DCWC-04-2X100-D0NB
Page 1: ......
Page 2: ...Sentry Switched DC PDU 2 of 211...
Page 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Page 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Page 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Page 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Page 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Page 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Page 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...