Function (Fct.)
Input Range
Description
C.6.0.0 Reset
C.6.1.0
Factory Reset
Confirm to reset.
Resets all parameters to their original
values. Device settings before the reset
will be lost. Service personnel only.
C.6.2.0
Customer Reset
Confirm to reset.
Resets parameters for all functions listed
in the table to their original values. Device
settings before the reset will be lost.
C.6.3.0
Restart
Confirm to reset.
If the device is not functioning properly,
this will restart the device.
* You can select these output functions if the device is configured for interface applications.
** See tables below
Menu items C.3.2.0 and 4.2.0: 4 mA setting range
Output function
Minimum value
Maximum value
Default
Level
0 m
< 20 mA setting for level
0 m
Level volume/ mass 0.00 m3/
0.00 Kg
< 20 mA setting for level volume/ mass
0 m³/
0 Kg
Distance
0 m
< 20 mA setting for distance
0 m
Interface level
0 m
< 20 mA setting for interface level
0 m
Interface distance
0 m
< 20 mA setting for interface distance
0 m
Interface volume/
mass
0.00 m3
< 20 mA setting for interface volume/
mass
0 m³
Ullage volume/
mass
0.00 m3/
0.00 Kg
< 20 mA setting for distance volume/ mass 0 m³/
0 Kg
Layer
0 m
< 20 mA setting for layer
0 m
Layer volume/ mass 0.00 m3
< 20 mA setting for layer volume/ mass
0 m³
Menu items C.3.3.0 and 4..0: 20 mA setting range
Output function
Minimum value
Maximum value
Default
Level
> 4 mA setting for level
Tank TBO + RO
Tank TBO -
BD
Level volume/ mass > 4 mA setting for level
volume/ mass
Max value in volume/ mass table Max value in volume/
mass table
Distance
> 4 mA setting for
distance
Tank TBO + RO
Tank RO
Interface level
> 4 mA setting for
interface level
Tank TBO + RO
Tank TBO -
BD
Interface distance
> 4 mA setting for
interface distance
Tank TBO + RO
Tank RO
Interface volume/
mass
> 4 mA setting for
interface volume/ mass
Max value in volume/ mass table Max value in volume/
mass table
Ullage volume/
mass
> 4 mA setting for ullage
volume/ mass
Max value in volume/ mass table Max value in volume/
mass table
Layer
> 4 mA setting for layer
Tank TBO + RO
Tank height - BD
Layer volume/ mass > 4 mA setting for layer
volume/ mass
Max value in volume/ mass table Max value in volume/
mass table
where,
BD is menu item C.1.9.0, Blocking Distance
RO is menu item C.1.10.0, Reference Offset
TBO is menu item C.1.11.0, Tank Bottom Offset
Summary of Contents for optiplex 1300 c
Page 1: ......
Page 49: ...Handbook OPTIFLEX 1300 C 49 OPTIFLEX 1300 C 1 Volume measurement of liquids...
Page 50: ...Handbook OPTIFLEX 1300 C OPTIFLEX 1300 C 50 2 Volume measurement of solids...
Page 51: ...Handbook OPTIFLEX 1300 C 51 OPTIFLEX 1300 C 3 Mass measurement of liquids or solids...
Page 62: ...Handbook OPTIFLEX 1300 C OPTIFLEX 1300 C 62 Finding the advanced setup menu...
Page 95: ...Handbook OPTIFLEX 1300 C 95 OPTIFLEX 1300 C Note...