51
MMC Smart Drive Hardware Manual
-
SYSTEM POWER DEVICES
4.3
Line Reactors
AC Line Reactors are required when using some models of the MMC Smart Drive.
They protect the drive from impermissible rates of current change and reduce
harmonic current distortions. When required, they are mounted between the drive and
the mains input power source.
Figure 4-1: Line Reactor Connection (Simplified)
Line reactors are not necessary for the 230V MMC Smart Drives or the 460V size 1
and 2 MMC Smart Drives. Line reactors are required for the 460V size 3 and size 4
MMC Smart Drives.
NOTE
Multiple drives or inverters on a common power line require one reactor per
drive. Individual reactors provide filtering between each drive (and thereby
reduce crosstalk) and also provide optimum surge protection for each unit. A
single reactor serving several drives does not provide adequate protection,
filtering or harmonic reduction when the system is partially loaded. Refer to
for an example of one line reactor connected to one drive.
WARNING
The frame of line/load reactors must be grounded at one of the reactor
mounting holes typically by using a star washer under the heads of the
mounting bolts. INJURY OR DEATH MAY RESULT IF THESE SAFETY
PRECAUTIONS ARE NOT OBSERVED.
Danger Electric
Shock Risk
MOTOR
C1
C2
B1
B2
A1
A2
MMC SMART DRIVE
LINE REACTOR
SCPD
L1 L2 L3
Summary of Contents for MMC Smart Drive Series
Page 2: ......
Page 10: ...8 Kollmorgen June 2014 MMC Smart Drive Hardware Manual TABLE OF CONTENTS...
Page 14: ...12 Kollmorgen June 2014 MMC Smart Drive Hardware Manual INTRODUCTION TO THE MMC SMART DRIVE...
Page 164: ...162 Kollmorgen June 2014 MMC Smart Drive Hardware Manual 460V 3 PHASE MMC SMART DRIVE NEXTGEN...
Page 286: ...284 Kollmorgen June 2014 MMC Smart Drive Hardware Manual S200 DLS DRIVE Figure 9 1...
Page 316: ...314 Kollmorgen June 2014 MMC Smart Drive Hardware Manual MOTOR CABLES CONNECTORS...
Page 368: ...366 Kollmorgen June 2014 MMC Smart Drive Hardware Manual DECLARATIONS OF CONFORMITY...
Page 369: ...Kollmorgen June 2014 367 MMC Smart Drive Hardware Manual DECLARATIONS OF CONFORMITY...
Page 370: ...368 Kollmorgen June 2014 MMC Smart Drive Hardware Manual DECLARATIONS OF CONFORMITY...
Page 371: ...Kollmorgen June 2014 369 MMC Smart Drive Hardware Manual DECLARATIONS OF CONFORMITY...
Page 372: ...370 Kollmorgen June 2014 MMC Smart Drive Hardware Manual DECLARATIONS OF CONFORMITY...
Page 384: ...MMC Smart Drive Hardware Manual INDEX 382 Kollmorgen June 2014...
Page 386: ...384 Kollmorgen June 2014 MMC Smart Drive Hardware Manual SALES AND SERVICE...