Kollmorgen - June 2014
23
MMC Smart Drive Hardware Manual
-
INSTALLING THE MMC SMART DRIVE
3.9.3
Bonding a Ground Bus or Chassis Using a Bolt
1.
Brush off any non-conductive materials (e.g. paint) from the threaded bolt (s).
2.
Slide a star washer over the threaded bolt (s).
3.
Use a subpanel having tapped mounting holes. Remove any non-conductive
materials from around the mounting holes on both sides of the subpanel.
4.
Turn the threaded bolts into the subpanel mounting holes.
5.
Slide a star washer onto the threaded end of the bolt.
6.
Turn and tighten a nut onto the stud.
7.
Slide a flat washer onto the threaded end of the bolt.
8.
Position the mounting holes on the groundbus or mounting bracket over the
threaded bolts and turn the bolts until they come through the grounding bus or
mounting bracket.
9.
Slide a star washer onto the threaded end of the bolt.
10. Slide a flat washer onto the threaded end of the bolt.
11. Turn and tighten a nut onto the bolt.
3.9.4
Grounding Multiple Drive Cabinets
1.
Mount one bonded ground bus in each cabinet.
2.
Designate the cabinet ground bus in one and only one of the cabinets as the com-
mon ground bus for all of the cabinets in the system.
3.
Connect the ground wires from the ground bus in each individual cabinet ground
bus to the designated common ground bus (mounted in only one of the cabinets).
4.
Connect the common cabinet ground bus to an external ground system that is
connected to a single point ground.
3.9.5
Bonding Multiple Subpanels
Kollmorgen recommends bonding both the top and bottom of subpanels sharing the
same enclosure. Use a 25.4 mm (1.0 in.) x 6.35 mm (0.25) wire braid. Be sure the
area around each wire braid fastener is clear of any non-conductive materials. Bond
the cabinet ground bus to at least one of the subpanels.
3.10
Drive Mounting Guidelines
•
A control cabinet for the MMC Smart Drive should have a NEMA-12 rating or bet-
ter. A cabinet with this rating protects its contents from dust and mechanical dam-
age.
•
The cabinet must be large enough to provide adequate air circulation for the MMC
Smart Drive and other components. Always allow for adequate air flow through
the MMC Smart Drive vents.
NOTE
Subpanels that are not bonded together may not share a common low im-
pedance path. This difference in impedance may affect networks and other
devices that span multiple panels.
Summary of Contents for MMC Smart Drive Series
Page 2: ......
Page 10: ...8 Kollmorgen June 2014 MMC Smart Drive Hardware Manual TABLE OF CONTENTS...
Page 14: ...12 Kollmorgen June 2014 MMC Smart Drive Hardware Manual INTRODUCTION TO THE MMC SMART DRIVE...
Page 164: ...162 Kollmorgen June 2014 MMC Smart Drive Hardware Manual 460V 3 PHASE MMC SMART DRIVE NEXTGEN...
Page 286: ...284 Kollmorgen June 2014 MMC Smart Drive Hardware Manual S200 DLS DRIVE Figure 9 1...
Page 316: ...314 Kollmorgen June 2014 MMC Smart Drive Hardware Manual MOTOR CABLES CONNECTORS...
Page 368: ...366 Kollmorgen June 2014 MMC Smart Drive Hardware Manual DECLARATIONS OF CONFORMITY...
Page 369: ...Kollmorgen June 2014 367 MMC Smart Drive Hardware Manual DECLARATIONS OF CONFORMITY...
Page 370: ...368 Kollmorgen June 2014 MMC Smart Drive Hardware Manual DECLARATIONS OF CONFORMITY...
Page 371: ...Kollmorgen June 2014 369 MMC Smart Drive Hardware Manual DECLARATIONS OF CONFORMITY...
Page 372: ...370 Kollmorgen June 2014 MMC Smart Drive Hardware Manual DECLARATIONS OF CONFORMITY...
Page 384: ...MMC Smart Drive Hardware Manual INDEX 382 Kollmorgen June 2014...
Page 386: ...384 Kollmorgen June 2014 MMC Smart Drive Hardware Manual SALES AND SERVICE...