RMS compact
9
Figure 5: Output Relay Pin configuration
There are three physical relay outputs on the RMS Compact, all of which are wired in a Normally Open (NO)
configuration. These relays are capable of switching mains voltage at a current of up to 5A (230 VAC, 30VDC)
each.
Software
The software shipped with RMS compact
is on CD-ROM. This CD-ROM contains the RMS compact
MIB file, the
Viewer/Programmer software, along with this manual and any other relevant tools (such as Terraterm Pro
terminal emulation software and SerialTFTP firmware upgrade program). The MIB will need to be compiled into
your NMS database.
Configuration Cable
Your package contains a configuration cable (DB9 female-to-female Null Modem). Use this cable to connect the
RMS compact
serial port and a dumb terminal or PC for configuration. When you configure the RMS compact
,
be sure to set the DIPswitch to the proper setting see the Installation section in this manual. Any dumb terminal
or terminal emulation package, such as Microsoft Windows 95/98/NT HyperTerminal will work fine, providing it
is capable of running at up to 38400 baud.
Power Supply
The type of power supply offered is:
Power Supply Type
Input
Output
Plug Top
230 VAC, 50 Hz
12 VDC, 500mA
Output 1
Output 2
Output 3
Com
NO
Com
NO
Com
NO
OUT 1
OUT 2
OUT 3