This screen enables the user to setup the circumstances by which an SNMP trap is generated in relation to the
contact closure inputs. Firstly traps can be ENABLED or DISABLED for an OFF to ON or an ON to OFF
transition, and also REPEAT TIMERS can be set if traps need to be continually send in an alarm situation.
Note
Note
Note
Note
:
The Minimum Setting for a Trap Repeat Timer is 30 seconds.
Temperature & Humidity Trap Configuration
Traps for the Temperature & Humidity inputs are setup by selecting the
Trap Setup
box connected to the
Analogue Inputs
window in the main configuration window. This will display the following window, whose
options are the same as the Contact Closure Trap options.
Figure 46: Temperature & Humidity Trap Configuration
Note
Note
Note
Note
:
The Minimum Setting for a Trap Repeat Timer is 30 seconds.
Logic Configuration Screens
The four central blocks on the main configuration window relate to the four logic outputs available within the
RMS compact
.
Selecting one of these blocks will display a window as follows (output 1 selected):