RMS compact
13
The figures below show an example of where the RMS compact could be mounted
Figure 10: RMS compact mounted without 19" Front plate
Cable Management
The RMS compact has a cable management tray attached to the casing of the unit. This enables the user to
route and attach cables to prevent any accidental disconnection.
Preparing to Configure
For configuration, connect the RMS compact
temporarily to a PC with a terminal emulation package such as
Terraterm, (contained on the RMS compact Cdrom), or to a dumb terminal capable of communicating at 38400
baud. The following steps guide you in connecting the RMS compact
to the network and UPS.
1. Adjust the DIPswitches on the RMS compact
for Configuration. Switch 1 down (ON); switch 2 up (OFF).
2. Temporarily, connect the RMS compact
adapter to a dumb terminal or to a PC with the terminal emulation
package.
a) Using the supplied configuration cable, connect one end of the cable into a dedicated RS-232 serial
port on the configuration PC.
b) Connect the other end to serial port 1 on the RMS compact
.
4. Configure the communications settings.
Use the following settings to configure the dumb terminal or PC.
Baud rate
Æ
9600
Flow Control
Æ
None
Data bits
Æ
8
Handshaking
Æ
None
Stop bit
Æ
1
Terminal Type:
Æ
ANSI (VT100)
Parity
Æ
None
Local Echo
Æ
Off
RMS compact
Mounting
screws