RMS compact
16
Note:
Note:
Note:
Note:
Invalid Addresses in the Trap Host table may cause problems with traps not being sent, SNMP SET
commands not working etc.
To enter values, enter the number of the option, Press
<enter>
. Enter your new value after the prompt
If you want to return to the
Main Menu
, press
10
and press
<enter>
.
For more information on IP addresses and net masks, see the Reference section of the
Appendix C
in this
manual.
Enabling Web Browser Access
To enable access for configuration and monitoring via a Web browser using HTTP, the user must enable HTTP
access in this menu. They must also assign a user name and password.
DHCP/BootP Setup
To enable the RMS compact to have an IP address automatically assigned by a DHCP or BootP server, select
option 9
Change boot type
and set for either DHCP or BootP operation. The
Card Host Name
field, is the
information that will be displayed on the DHCP server to identify the RMS compact unit.
Net Access Configuration
This section configures the Telnet and passthrough options for the RMS compact
:
Knuerr RMS compact version X.X.X
Embedded Agent Setup
1. Telnet Configuration
2. Serial Port 1 Configuration for pass-thru
3. Exit Net Access Setup
Enter choice (ESC to exit):
Figure 13 Net Access Configuration Group
Telnet Configuration
Selecting option 1 in the above menu will display the following sub-menu:
Knuerr RMS compact version X.X.X
Embedded Agent Setup
Telnet: enabled
password:
inactivity timeout: 30 seconds
passthru port: disabled
passthru terminator: 0
1. [en/dis] Telnet Access
2. Set Telnet Access Password
3. Set Telnet Inactivity Timeout
4. Set Pass-thru Port
5. Set Pass-thru Terminator
6. Exit Telnet Setup
Enter choice (ESC to exit):
Figure 14 Telnet Configuration screen
This menu is used to enable/disable Telnet access to the RMS Compact, also to set a Telnet username and
password. The RMS compact
also has the ability to make a ‘passthrough’ connection to a device attached to
the serial port – this section sets the serial port to be used for this purpose.
Pass-thru port parameters
Option 2 in the Net Access menu deals with the actual configuration details of the serial port when used in
passthrough mode (see above). Selecting option 2, will display the following menu:
Knuerr RMS compact version X.X.X
Embedded Agent Setup