RMS compact
37
Figure 47: Logic Configuration Screen
The inputs are displayed on the left of the screen – to select an input to be used in this logic calculation, select
Add New Input
from the
Inputs
drop down menu. The user then selects the type of logic operation (AND or
OR), followed by any delays that need to be introduced - the user may introduce a delay before the output is set
(to allow for rapid or erroneous changes in input condition). The same is true for clearing of an output once the
condition has cleared. These timers are set by selecting the ‘ ON
Time Delay’
or ‘OFF
Time Delay’
.
Note:
Note:
Note:
Note:
Although there are only 3 relay outputs on the RMS Compact, there are 4 possible logic calculations
available. The calculations 1 –3 relate to the physical outputs, whilst number 4 is a purely logic based
calculation used for generating traps based upon a pre-defined set of input parameters
.
PLEASE NOTE :
NOR logic operations are not supported by the firmware
Output Trap Configuration
The second from right box configures the output trap parameters as follows:
Figure 48: Logic Output Trap Configuration