SYSTem Command
PCR-WE Interface Manual
269
SYST:EXT:SIGOUT:MAP
Maps SIGNAL OUT channels (STAT.1 to STAT.3).
Command
SYSTem:EXTernal:SIGOUT:MAP <NRf_port>,<character_map>
SYSTem:EXTernal:SIGOUT:MAP? <NRf_port>
Parameter
<NRf_port>
Value 1 to 3 Channel number to be mapped (STAT.1 to STAT.3)
Parameter
<character_map>
Value:
DISabled
Disabled (default)
OUTON
Output on status
IPKLIM
Current peak limit status
OVERLOAD
Overload status
BUSY
Busy status
WIRING_1P
Output method status (single-phase)
WIRING_1P3W Output method status (single-phase three-wire)
WIRING_3P
Output method status (three-phase)
VRANGE-H
Output voltage H range status
POWON
POWER switch on status
SEQSTAT
Sequence/power line abnormality simulation status
USERPROGOUTProgrammable signal status
Example
SYST:EXT:SIGOUT:MAP 1,BUSY
Response: Characters