8.5. Kentix Power-Adapter (KIO3) with digital I/O clips
The Kentix I/O Power-Adapter is used to expand your Kentix-solution to include the additional functions:
• Connecting of up to two external alarms via dry contacts to a MultiSensor
• Controlling resp. switching of up to two external devices via relays by a MultiSensor
The adapter is connected directly to the Kentix system jack and offers the possibility to power the MultiSensor
with a power plug or a permanently connected AC adapter.
The cable length between MultiSensor and the KIO3 adapter should not exceed 10m.
The relays are equipped with PDT contacts and can be loaded with up to 60VDC/3A.
Figure 1: Back of Kentix Power-Adapter (KIO3)
Figure 2: Circuit diagram with external alarms
Page
(07-2018, subject to change)
kentix.com