14.4. Data sheet MultiSensor-LAN-RF (KMS-LAN-RF)
Connectable devices
Stand-Alone operation (integrated web server)
AlarmManager-PRO
Sensor - temperature
range -20 to 99°C / -3 to 210°F (exactness ± 0,5°)
Sensor - Relative humidity
range 0 to 100% (exactness ± 3%)
Dew point
calculated in °C/°F
Sensor - motion
PIR sensor, trigger sensitivity configurable
detection cone: approx. 110°
range: approx. 8m
Sensor - vibration
3 axes vibration sensor (adjustable)
Sensor - carbon monoxide (CO)
0-10.000ppm measurement ± 10%
Internal resolution: 20-200ppm (0-100%)
lifetime 10 years
Buzzer
85dB, 2.3kHz
Sensor - external alarm input
2 x alarm input (e.g. Armed-Active, Always-Active)
Both for external dry contacts via separately available KIO1/
KIO3 power adapter
External alarm output
2x alarm output (e.g. Armed-Active, Always-Active),
connection via separately available KIO3 power adapter
LED
ALARM (red), RUN (green)
LINK/ACT at the LAN jack
LAN
10/100Mbit LAN connection
integrated web server
Radio
ZigBee® 2,4GHz ISM band +3dBm output power,
IEEE802.15.4, encryption AES 128 Bit
SNMP
(Simple Network Management
Protocol)
SNMP V2 (write/read)
SNMP Traps
power supply with PoE
12-72VAC/DC power consumption ca. 1.5W, PoE class 1
power supply with power supply unit
12-32VAC/DC power consumption ca. 1.5W over system jack
KENTIX system jack
RJ45, for supply and connection of external IO-modules
(KIO1/KIO3)
Chassis
Material: PS 90 x 90 x 45 mm, Weight: approx. 100g
Color: White, Black
Environmental conditions
Temperature 0 - 50°C / 32 - 122°F
Humidity 5-95%, non-condensing
Types
KMS-RF-B (Chassis Black)
KMS-RF-W (Chassis White)
Content of delivery
Mount bracket, Mount material
Accessories
PoE Injector (KPOE150S)
Power-Adapter with power supply (KIO1, 2, 3)
Leakage sensor (KLS03)
Approvals
CE
Page
(07-2018, subject to change)
kentix.com
111