14.14. Data sheet SmartMeter (KSM-DR60-RF / KILM-x-xx)
Connectivity
Kentix PowerManager
Number radio counter
Up to 32 radio counter on one PowerManager
Power supply
1/3 x 230/400V (Neutral) +/-10%, input approx. 1,5W
Power metering
60A per Phase
Metering Accuracy
< 2%
Resolution
1 W
Frequency
45 - 65 Hz, 0,01 Hz
Measured values
Voltage (U), current (I), apparent power (S), active power (P),
reactive power (Q), active factor, consumption (kWh)
LED
Teach signaling
Radio
2,4 GHz, encoding AES 128 Bit
reach up to approx. 30m
Clamps
Screws, diameter 5,5mm (up to 16 mm
2
)
Casing
DIN rail mounting, 4HP, protection class IP2071 x 97 x 70 mm,
color: RAL7035
Environmental conditions
Temperature -10°C to 50°C, Humidity 5-95%,
not condensed
Types
KSM-DR60-RF (Online SmartMeter)
KILM-1-16 (Online InlineMeter 16A, 1-phase)
KILM-3-16 (Online InlineMeter 16A, 3-phase)
KILM-1-32 (Online InlineMeter 32A, 1-phase)
KILM-3-32 (Online InlineMeter 32A, 3-phase)
Delivery
SmartMeter, magnetic antenna
Approvals
CE
Page
(07-2018, subject to change)
kentix.com