background image

            

5.10.   User accounts

In the user accounts the setup of the permissions and the alarming is done.
Only if the required user data is entered, a user can control the AlarmManager or request information.
The list describes the user data required for AlarmManager interaction: 

Kentix360 cloud access

A mobile access to the AlarmManager via the Kentix360 cloud service can be activated for each user account. 
The option „Kentix360 cloud access“ activates a button „Setup app access“ where the users individual cloud ID 
is displayed.

After the first login with the smartphone alarms are also reported to the user as push notification.
Additionally messages are also send via e-mail and SMS, if activated.

Input field

Description

User Password

Login to the Web-Interface and the Kentix App

E-Mail Address

Destination address for the alarming

Phone number

Destination phone number for the alarming

PIN-Code - RFID-Token

Remote control by SMS and switching via KeyPad

User level

Authorization level for working with the system

Notification

Defines which type of alarms and and ways of alarming are used for this user

Assigned alarm zones

The user can only switch zones assigned to his account. To switch all zones together, every zone has to 
be assigned to the user.

Page 

                                                               (07-2018, subject to change)

kentix.com

20

IMPORTANT!

Only users with the permission „Administrator“ are allowed to make changes to the AlarmManager.

For users without the admin permission, only the tab pages „Dashboard - Logbook - Chart“ are available for 
viewing purposes.
Power failures and connection interrupts to the sensors are also only reported to users marked as 
„Administrator“.

  

Al

a

rmMa

n

a

g

e

r

 

Sm

a

rt 

Mo

n

ito

ri

n

g

     

Summary of Contents for AlarmManager-BASIC

Page 1: ...360 Smart Building Security for Pros kentix com User Manual...

Page 2: ...9 Configuration Dashboard Logbook Time profiles 17 5 9 1 Add edit MultiSensors 17 5 9 2 Manage alarm zones 18 5 9 3 Quitting alarms 19 5 10 User accounts 20 5 11 Kentix360 Cloud 21 5 12 Configuration...

Page 3: ...application examples for Power Adapters KIO1 3 48 8 7 Kentix Alarm siren KFLASH1 49 8 7 1 Configuration 49 8 8 Kentix IO Modules 50 8 9 MultiSensor LAN RF LAN ZigBee Repeater 51 9 Smart Access Introdu...

Page 4: ...22 System Import Export 89 9 6 2 23 System Help 89 9 6 3 Master Slave mode Compound operation with multiple AccessPoints 89 9 6 4 Reset of components 89 9 6 5 Battery replacement 90 9 6 6 Emergency op...

Page 5: ...or KMS Door 112 14 6 Data sheet KeyPad KKPT 113 14 7 Data sheet AccessPoint KXP 16 114 14 8 Data sheet Online Door knob DoorLock DC KXC KN1 2 3 115 14 9 Data sheet DoorLock LE KXC LE 116 14 10 Data sh...

Page 6: ...etwork PoE or power plugs respectively If further steps for installation are necessary e g DoorLock components these will be explained in detail Follow the overview in the table of contents Configurat...

Page 7: ...the AlarmManager are not lost Energized relays drop out and go back when the power returns in the unswitched output state The device sends power outages directly via SMS The internal energy supply can...

Page 8: ...lt IP Address 192 168 100 222 into your web browser 4 Enter default user admin password and click Login pay attention to your own IP settings 5 Adjust IP address of AlarmManager in settings 6 Add wire...

Page 9: ...e Sensor The connection of a Leakage Sensor is realized either by a direct connection to an AlarmManager MultiSensor LAN or with a KIO1 Power Adapter required for a connection to a MultiSensor RF The...

Page 10: ...rchanged Example 1 Power supply of one MultiSensor via the system jack of the AlarmManager Example 2 Power supply of two MultiSensors via Power Adapter KIO1 and plug power supply Electronic equipment...

Page 11: ...d and other devices can be connected The PRO Version supports up to 500 devices The Kentix RF components communicate via ZigBee radio in the 2 4GHz ISM Band The wireless MultiSensors work in a mesh ne...

Page 12: ...racket can be removed without any tool by lifting the latch Afterwards the tray can be unlocked and opened The SIM card is placed inside the opened part of the holder Page 07 2018 subject to change ke...

Page 13: ...guration use Default IP address 192 168 100 222 user name admin and password password Page 07 2018 subject to change kentix com 13 NOTICE Only users with the permission Administrator are allowed to ma...

Page 14: ...f AlarmManager and MultiSensors firmware update TCP 80 443 from PC to AlarmManager MultiSensor 2 Data transfer between MultiSensors and AlarmManager TCP 80 443 bidirectional 3 Request of measurement v...

Page 15: ...Pad Note that the KeyPad allows only 4 digit passwords To use the internal RFID card inside a KeyPad also enter the RFID card number The RFID card number can also be read out via a KeyPad To do so pre...

Page 16: ...e settings Constant of 1 Second System has been disarmed Constant of 3 Seconds Arming was not executed alarms are existing Please check external alarm inputs on AlarmManager or MultiSensor MultiSensor...

Page 17: ...KeyPad Touch must be assigned directly to the respective device AlarmManager or MultiSensor LAN RF during this process For all other devices this is not necessary Here the assignment to an alarm zone...

Page 18: ...ve alarms each alarm zone can be assigned a timer profile for timed activation deactivation The arming delay allows you to set a time between arming and first alarm activation The acoustic feedback bu...

Page 19: ...s quit without the cause being fixed the AlarmManager stops the alarm repetition The alarm state stays active Additionally the AlarmManager tries for every 6 hours to quit existing alarms When the cau...

Page 20: ...ogin to the Web Interface and the Kentix App E Mail Address Destination address for the alarming Phone number Destination phone number for the alarming PIN Code RFID Token Remote control by SMS and sw...

Page 21: ...on the e mail server an encryption with an associated port must be selected When selecting an encryption type STARTTLS SSL the corresponding standard port is automatically entered as well If necessar...

Page 22: ...d in the web interface e g arm disarm alarm1 armed active alarm2 always active fire server state sensors MultiSensors IO modules SmartMeter Query branch for the values of all connected sensors All val...

Page 23: ...2B49 myText Text message with up to 160 characters Up to 320 characters possible In this case 2 Messages will be sent HTTP return code 200 when SMS sending was successful 300 when SMS sending was unsu...

Page 24: ...pective device variant An AlarmManager BASIC can be converted to an AlarmManager PRO by entering a license key to extend the functionality if required For information on the scope of functions or diff...

Page 25: ...d between 60 and 999 seconds Please note that the alarm is first triggered after at least 2 failed attempts Network cameras When an alarm is triggered the AlarmManager can control cameras connected to...

Page 26: ...website You can find the firmware in the section Download Support Software and manuals 2 Log in to the web interface of your device and go to the section System System functions 3 Always create a back...

Page 27: ...dividual sensors To get an optimal sensitivity and function of the sensors please note the following installation instructions Note the following instructions Do not install close to heaters or direct...

Page 28: ...e available for connecting external devices or external alarms with inputs or outputs 1 Power Adapter KIO 1 power supply 2 digital inputs 2 Power Adapter KIO 3 power supply 2 digital inputs and 2 rela...

Page 29: ...255 255 0 User password admin password 6 6 2 Software function MultiSensor LAN In the following the stand alone functionality of the integrated web server is described For the described functionality...

Page 30: ...d alarm conditions This display will be actualized all 5 seconds Page 07 2018 subject to change kentix com 30 NOTE The Sensor records a value for temperature and humidity every 10 minutes Additionally...

Page 31: ...bout 10ppm There is no exact measurement of the CO content The measurement is construed to the highest sensitivity and can be changed slightly in the adjustment Carbon Monoxide concentrations like the...

Page 32: ...he Kentix MultiSensor LAN You can select between German and English language Temperature unit Changes the temperature evaluation and display of the MultiSensor LAN between Celsius and Fahrenheit Commu...

Page 33: ...ngth SNMP settings Configuration of the Simple Network Management Protocols The MultiSensor LAN is able to send alarm messages as SNMP Traps Enter both SNMP host addresses for this Further the sensor...

Page 34: ...ter in this guide Wireless settings ZigBee MultiSensor LAN RF This section displays information about the current ZigBee wireless network In addition the radio channel can be changed here and the radi...

Page 35: ...he ControlCenter Updating the device is not necessary possible Interior view MultiSensor Door Page 07 2018 subject to change kentix com 35 LED red green Top of sensor case Normal running mode LED red...

Page 36: ...MultiSensor can be installed at the door frame or window frame and instead the magnet at the moveable part when using the reed contact keep the distance to the magnet below one centimeter only use su...

Page 37: ...a wiring is not necessary To ensure the functionality of the contact take care to not exceed the maximum distance of one centimeter between magnet and casing and orientated to one side of the casing...

Page 38: ...nly possible if the door or window is closed and the sensor has detected the magnet Arming attempts are otherwise directly terminated If the equipped door has to be opened during arming the option Arm...

Page 39: ...not on moving parts door leaf window leaf 6 7 6 Test of the settings The alarming function of the MultiSensor Door can be tested by simply opening closing door or window This will trigger a direct upd...

Page 40: ...or the complete system 7 1 Adding a KeyPad 1 For adding a KeyPad to the AlarmManagers configuration start the teach in process in the AlarmManagers Dashboard and press the learn button on the back of...

Page 41: ...ctly in front of the X Learn User RFID cards New RFID cards are added via the user configuration In the user s settings select the next to the RFID card field and select the KeyPad Then press one of t...

Page 42: ...ble of the leakage sensor into one of the System jacks of the AlarmManager The powering and alarming is done directly via the AlarmManager With the ControlCenter enter a suitable name for the external...

Page 43: ...d cable lenth should not exceed 50m It is important to code the according sensors as intermediate or end device For this purpose a micro switch is located inside the casing Page 07 2018 subject to cha...

Page 44: ...detector to detect leaks with a single sensor over a length of up to 20 meters The KLS03 ROPE works in the same way as the standard KLS03 It also has the sensor electrodes at the lower side of the ho...

Page 45: ...he MultiSensor with a power plug or a permanently connected AC adapter The cable length between MultiSensor and the KIO1 adapter should not exceed the following lengths Power supply only up to 50m Pow...

Page 46: ...an external power supply This can be necessary e g if no PoE Switch is available for the operation of a MultiSensor LAN LAN RF or when a MultiSensor RF shall be connected separately to monitor the ext...

Page 47: ...a MultiSensor The adapter is connected directly to the Kentix system jack and offers the possibility to power the MultiSensor with a power plug or a permanently connected AC adapter The cable length b...

Page 48: ...lock Digital inputs 0 Digital outputs 0 Power supply AC adapter Power supply for one MultiSensor RF LAN LAN RF Connection of one MultiSensor RF to monitor the external power supply Power supply for a...

Page 49: ...he power supply is done via a Power Adapter KIO2 which is connected to the opposite side of the T Adapter When also the alarm input of the connected MultiSensor shall be used e g by connecting a leaka...

Page 50: ...s and B GND Use the supplied power adapter cable 2 Open the Web Interface of the module via the default IP 192 168 255 1 and change the IP settings in Network Settings to your required settings Defaul...

Page 51: ...possible to realize a connection to distant RF Components MultiSensor RF Door KeyPads via LAN WAN The configuration of the repeater and the connected components is done via the web interface of the A...

Page 52: ...ustry and trade Banks Authorities and hospitals Telecommunication Chambers and practices Energy and water supplier 9 3 Safety instructions The installation of the AccessPoint and all DoorLock componen...

Page 53: ...e programming card set This card set is required only once per system Multiple DoorLock devices are put into operation with the same card set The cross linking of one or several doors is done via the...

Page 54: ...ll reader expands Kentix DoorLock with additional application fields such as factory doors doors with motor control or barriers It integrates completely into the DoorLock series with Online knob and o...

Page 55: ...terSet comes with an IP Wall Reader a network relay module and three RFID tokens This set can be combined with one additional Extension Reader only IP Wall reader without network relay module in order...

Page 56: ...is required per system installation which consists of these 4 cards System card Servicekey card Battery change card Dismantling card The AccessPoint is the central component of the access solution On...

Page 57: ...ofile cylinder is delivered with a new forend screw 2 Insert the Kentix profile cylinder into the door Insert and fix the new forend screw The mechanical knob is already mounted at the profile cylinde...

Page 58: ...etely over the fixing pin and into the square pin fixture of the lever 1 Insert the spiral pin 2 into the square pin and completely press it into it using a pliers Step 2 Put on square pin Insert the...

Page 59: ...electric door lever once again into the square nut of the lock Insert the handle holder of the mechanical door lever from the other side and screw it along with the electronic door lever through the d...

Page 60: ...oor levers pointing to the left Step 7 Fasten mechanical lever Insert the locking screw from the bottom of the rosette and tighten it Step 8 Check functionality Check the functionality and easy moveme...

Page 61: ...of the relay at the wall reader Power supply and the relay are connected directly to the wall reader Please follow the PIN assignment as shown on the diagram below 9 5 3 2 Commissioning with wiring o...

Page 62: ...connected power supply can be used connected to PINs 5 6 if necessary Page 07 2018 subject to change kentix com 62 NOTE The wall reader is always installed with a fix wiring to an external power supp...

Page 63: ...ibed in the following Step 1 Installation in the flush box Connect the wall reader to the flush mounted socket Ensure that no cable is pinched or squeezed Step 2 Fasten wall reader Align the wall read...

Page 64: ...der is already preassembled in a 2 part surface mounted housing The lower housing part is mounted on the wall using the supplied screws Then the connection cable is inserted through the cable inlet an...

Page 65: ...osing lever 5 Operating lever 6 Mounting screw 7 Wakeup button 8 Battery 9 Battery compartment To open the battery compartment a special key is required which is available separately For the different...

Page 66: ...rection is determined by the position of the small screw at the mounting thread Screw at the side of the mounting thread Opening by turning the lever to the left Page 07 2018 subject to change kentix...

Page 67: ...the door and fix it with the fastening nut and fastening screw Then install and fasten the locking lever and safety washer with the locking nut Page 07 2018 subject to change kentix com 67 NOTE If nec...

Page 68: ...k must be activated by pressing the button at the lock This is necessary for the initial setup and also the normal operation Press the button until the LED lights up Then hold the RFID key in front of...

Page 69: ...are required for the addressing The first IP Wall Reader connected to a network relay module always has the device address 1 So here dip switch no 1 has to be set to ON Using a second reader the read...

Page 70: ...sh mounted installation Screw the wall bracket onto a DIN device box with a screw distance of 60mm using the supplied screws Page 07 2018 subject to change kentix com 70 Reader unit Terminal connector...

Page 71: ...ews Dimensions in millimeters Page 07 2018 subject to change kentix com 71 Reader unit locking bar wall mount chassis connecting cable If cables are fed from the top or bottom of the housing the corre...

Page 72: ...stallation into a separate DIN wall device connection box or to a DIN rail bracket The module has two terminal blocks The PINs are connected as shown in the following Page 07 2018 subject to change ke...

Page 73: ...Wall Reader and network relay module The configuration of the two devices is done via the web interface of the network relay module This configuration is based on the same structure as on the Kentix A...

Page 74: ...The Online knob is delivered in opened state with the a loosely mounted knob cover The cover can be easily pulled down from the knob One of the two batteries is blocked by a plastic lock This lock has...

Page 75: ...ait for 5 seconds 3x langer Ton 1x short sound 1x long sound 2x short sound LEDs light up green then wait for 5 seconds 2x short sound LEDs light up green then wait for 5 seconds Page 07 2018 subject...

Page 76: ...for 5 seconds then the next card can be directly learned 1x short sound 1x long sound No Step Note Signalization 1 Present Servicekey card yellow in front of DoorLock devices reader unit to start the...

Page 77: ...AccessPoint and firmware update via web browser TCP 443 HTTPS 80 HTTP redirected to 443 from PC to AccessPoint 2 Communication configuration of multiple AccessPoints with each other Master Slave mode...

Page 78: ...h date time and the respective user Via the magnifying glass icon in the upper right different filter functions can be applied to the logbook 9 6 2 4 Dashboard DoorLock control Overview of all availab...

Page 79: ...r permission levels available The user level has no effect on the access permissions at the doors Userlevel Description Remote Access Only Access to bookings of assigned doors in the logbook Remote co...

Page 80: ...knob that require a replacement It is important that a valid e mail address has been entered in the user data Access profiles Sets the access authorization for the user The times for the access author...

Page 81: ...ch the user shall have permission to access the assigned doors The week plan can be edited in 15 minute steps Single fields can be selected by clicking a range of fields can be marked by clicking and...

Page 82: ...igured to stay permanently engaged The door can then be opened without a booking at the RFID reader For this operating mode a time profile can be chosen here which determines the times to which the do...

Page 83: ...Point and AlarmManager 2 In the AccessPoint section Configuration Communication the AlarmManager must be entered with IP address and a valid user 3 An alarm zone must be selected for the Online knob d...

Page 84: ...ith certain guidelines length upper lower case numbers special characters NTP 1 NTP 2 In the fields NTP 1 and NTP 2 the time servers for the time synchronization are defined This can be servers in the...

Page 85: ...with public e mail servers which require a user authentication Also the selection of an encryption method STARTTLS SSL is possible The communication port can be changed if necessary Please note that o...

Page 86: ...which is able to deliver pictures via a HTTP command Enter a name for the camera for example the installation place as well as the camera specific data IP address user data and select the camera loca...

Page 87: ...fined for the available user levels of the AccessPoint Specify a path for each of the levels Access Only Access Administrator and Super Administrator The required paths are individual depending on the...

Page 88: ...he AccessPoint can be uploaded here if necessary Select the firmware image file via the file dialog and press Start update 9 6 2 21 System SD card This is the administration for an SD card inserted in...

Page 89: ...RFID cards except the Servicekey card A deletion of the Servicekey card is not possible For the reset please proceed as described here After the reset the DoorLock device can be configured again At t...

Page 90: ...ith thumb and forefinger To complete the process the battery changing card has to be held in front of the knob once again To replace the batteries at a door lever the Allen screw has to be opened on t...

Page 91: ...9 6 7 Dismantling Using the dismantling card the knob can be pulled off from the profile cylinder There are no extra tools required To remove the knob hold the dismantling card in front of it The kno...

Page 92: ...enters 10 3 Safety instructions Installation In order to ensure the safety and integrity of the operator as well as the correct operation of KENTIX Smart Metering components the installation must be c...

Page 93: ...switch The web interface can then be used to change the basic settings such as IP data as well as the configuration of user data and counter settings A description of the configuration can be found l...

Page 94: ...s 2 Place the radio smart meter on the DIN rail Make sure that it engages correctly 3 Remove 11mm of the cable insulation at the supply and output lines with a suitable wire stripper 4 Connect the cab...

Page 95: ...supply PoE Power over Ethernet Default IP Adress 192 168 100 224 Subnet Mask 255 255 255 0 User password admin password No Description 1 Interrupt power supply For the duration of the electrical work...

Page 96: ...indicates whether there are currently alarms e g Threshold exceeded pending as well as the current torque consumption total consumption and PUE value Power Usage Effectiveness No Description Port Numb...

Page 97: ...address entered which is similar to the serial number printed on the Smartmeter Then click on the arrow next to the Smartmeter address This starts the search for new smart meters on the PowerManager O...

Page 98: ...must be entered here This has no function for the operation of the system User password All users who should have access to the PowerManager require a login user password in addition to the user name...

Page 99: ...fields NTP 1 and NTP 2 the time servers are set to synchronize the time These can be servers in your own network as well as public time servers default The time is needed to use the time profiles and...

Page 100: ...nfigured here If you have configured a DNS server in the DNS settings you can use the DNS name of the e mail server here By using ESMTP you can enter the e mail credentials provided by your e mail pro...

Page 101: ...the radio network can be reset here 10 5 4 13 System Help Contains support information and version information about PowerManager NOTICE The backup always includes the complete configuration including...

Page 102: ...assign a unique name to differentiate multiple profiles devices and enter your user password Page 07 2018 subject to change kentix com 102 NOTE Connections to the Kentix360 cloud only work together w...

Page 103: ...he overview for the devices configured in this zone Here the alarm zone can be switched separately Logbook Tapping the menu icon opens the selection menu There the logbook can be accessed The logbook...

Page 104: ...ontrol always shows all DoorLock devices doors configured in the system In order to be able to directly access frequently used doors for a remote opening these doors can be marked as favorites here To...

Page 105: ...anager or the AccessPoint Activation via telephone support or e mail is not possible To use the cloud an AlarmManager BASIC PRO or an AccessPoint is required MultiSensor LAN is not intended for operat...

Page 106: ...connected can be temporarily deactivated or deleted completely Kentix360 Account In the section Account the data of your Kentix360 cloud account and the corresponding user data is administrated Excep...

Page 107: ...card login to your AlarmManager and go to Kentix360 Login with your account data or create a new Kentix360 account Then register your AlarmManager for the cloud service chargeable charged by Kentix Cl...

Page 108: ...802 15 4 encryption AES 128 Bit LAN 10 100Mbit Integrated GSM Modem Quad Band GSM 3G 850 900 1800 1900MHz integrated SIM card holder SD card Integrated micro SD card holder as additional storage for i...

Page 109: ...wer adapter Ext output 2x alarm output e g Armed Active Always Active connection via separately available KIO3 power adapter LED ALARM red RUN green Radio ZigBee 2 4GHz ISM band 3dBm output power IEEE...

Page 110: ...parately available KIO3 power adapter LED ALARM red RUN green LINK ACT at the LAN jack LAN 10 100Mbit LAN connection integrated web server SD card Integrated micro SD card holder as additional storage...

Page 111: ...e connection via separately available KIO3 power adapter LED ALARM red RUN green LINK ACT at the LAN jack LAN 10 100Mbit LAN connection integrated web server Radio ZigBee 2 4GHz ISM band 3dBm output p...

Page 112: ...distance approx 1cm Buzzer 65dB 2 3kHz LED Multicolor LED Red Green ALARM Red Teach in Green Radio ZigBee 2 4GHz ISM band 3dBm output power IEEE802 15 4 encryption AES 128 Bit Power supply Battery 1x...

Page 113: ...rs depending on the number of switching cycles Chassis Material PS 135 x 90 x 19 mm Weight ca 100g Color High White Protection class IP40 Environmental conditions Temperature 0 45 C 32 113 F Humidity...

Page 114: ...reless DoorLock 868MHz Encryption AES 128 Bit Distance up to 25m up to 16 DoorLock devices per AccessPoint Power supply PoE 12 72VAC DC Power consumption approx 3W PoE class 2 Power supply System conn...

Page 115: ...m 3V Battery life up to 45 000 operations or up to 4 years Dimensions knob KXC KN1 IP55 length 42 7mm diameter 40 0mm KXC KN2 IP66 length 20 0mm diameter 45 0mm KXC KN3 IP66 outside IP55 inside length...

Page 116: ...ngagement possible without additional power consumption Power supply Battery CR123A Lithium 3V Battery life up to 100 000 operations or up to 6 years Dimensions door lever Compatible with all current...

Page 117: ...or exposed Power supply 10 32VDC or 10 24VAC Power consumption typ 0 8W max 5W Switching relays max 30V AC DC max 1 5A Dimensions length 71mm width 71mm H he 26mm diameter 60mm for flush mount box Ma...

Page 118: ...age Installation in cabinets with a door thickness of up to 20mm suitable for wooden steel and aluminium doors different locking levers included Power supply 1 Battery AA Lithium 3 6V Up to 100 000 op...

Page 119: ...33 mm Installation in switch box or on DIN rail LED RED GREEN BLUE Signaling LED Acoustic signal RGB illuminated field Connection Wall Reader Via relay module 4 wire length up to 500m up to two wall...

Page 120: ...GHz encoding AES 128 Bit reach up to approx 30m Power supply PoE 12 72VAC DC input approx 1 5W PoE class 1 Power supply system port 12 32VAC DC input approx 1 5W via system port KENTIX system port RJ4...

Page 121: ...r consumption kWh LED Teach signaling Radio 2 4 GHz encoding AES 128 Bit reach up to approx 30m Clamps Screws diameter 5 5mm up to 16 mm 2 Casing DIN rail mounting 4HP protection class IP2071 x 97 x 7...

Page 122: ...IP PORT 502 Default Security ID Password and IP Filter Terminals Plug able screw terminal for cables up to 1mm Inputs Digital wet inputs ON 10 50VDC OFF 4DC Input impedance 10kOHM Over voltage protec...

Page 123: ...s alarm systems etc Configuration Build in Web Server HTTP Default IP 192 168 255 1 Admin Admin Protocols KAM IO communication via IP PORT 502 Default Security ID Password and IP Filter Terminals Plug...

Page 124: ...ult IP 192 168 255 1 Admin Admin Protocols KAM IO communication via IP PORT 502 Default Security ID Password and IP Filter Terminals Plug able screw terminal for cables up to 1mm Inputs 8 differential...

Page 125: ...en Connectors 2 x RJ45 for standard patch cables Power supply Via Kentix system jack RJ45 Daisy chaining linking Up to 5 sensors max 50m combined cable length Chassis Material PS 80 x 80 x 80 mm Weigh...

Page 126: ...ensure the clean operation For AlarmManager and MultiSensors the following check list can be used It can also be used as an acceptance report for the system handover to the customer Page 07 2018 subje...

Page 127: ...l time controlled Vibration alarm from AlarmManager and MultiSensors when used E mail SMS alarming Push notification External alarm inputs on AlarmManager External switching outputs AlarmManager SNMP...

Page 128: ...disarm Keypad 3 Test arm disarm Leakage sensor 1 Fluidity contact alarm trigger Leakage sensor 2 Fluidity contact alarm trigger Leakage sensor 3 Fluidity contact alarm trigger No Type Place of install...

Page 129: ...manual is not a copyright violation but serves as an illustrative reference Even if these are not at the appropriate places marked as such the relevant statutory provisions The trade names and logos a...

Reviews: