8.6. Overview and application examples for Power-Adapters (KIO1-3)
Image
Description
Application examples
Power-Adapter with digital I/O clips
Adapter block for the connection of
2 MultiSensor-RF to a power supply via the
Kentix system jack.
Additionally a terminal block for using the
alarm inputs at one MultiSensor is available.
Terminal block:
•
Digital inputs: 2
•
Digital outputs: 0
•
Power supply: Terminal block or
AC adapter
•
Operation of one Kentix leakage
sensor at a MultiSensor-RF
•
Connection of external
components to the alarm input of
a MultiSensor (e.g. air
conditioning, door contact)
Power-Adapter
Adapter block with AC adapter for powering
one Kentix MultiSensor via the Kentix
System jack.
Terminal block:
•
Digital inputs: 0
•
Digital outputs: 0
•
Power supply: AC adapter
•
Power supply for one MultiSensor-
RF/-LAN/-
LAN-RF
•
Connection of one MultiSensor-RF
to monitor the external power
supply
•
Power supply for a Kentix Alarm
sirene plus one MultiSensor-RF/-
LAN/-LAN-RF via a RJ45 T-
Adapter (included with Alarm
sirene)
Power-Adapter with digital I/O clips
Adapter block with 2 digital inputs and
2 relay-outputs and 2 Kentix System jacks
for the connection of MultiSensors.
Terminal block:
•
Digital inputs: 2
•
Digital outputs: 2
•
Power supply: Terminal block or
AC adapter
•
Connection of external
components to the alarm input of
a MultiSensor (e.g. air
conditioning, door contact)
•
Connection of a LED to display
the arm/disarm state via the 1st
sensor output (relay 1)
•
Connection of a door control to
open a door when disarming an
alarm zone
KIO3
KIO1
KIO2
Page
(07-2018, subject to change)
kentix.com