5.14. Further devices / sensors
The Kentix AlarmManager offers the possibility to include other network devices into the monitoring as well.
These are added to the configuration like a MultiSensor via the dashboard.
To do this, select "+" in the alarm zone header area to add a new device to the respective zone.
Server Livecheck
Define here network devices that are to be monitored for availability using one of the two service types ICMP
Ping or Portcheck.
The AlarmManager cyclically checks whether a request on the service provides a positive response.
The polling interval can be freely defined between 60 and 999 seconds. Please note that the alarm is first
triggered after at least 2 failed attempts.
Network cameras
When an alarm is triggered, the AlarmManager can control cameras connected to the network and record image
data. The images are then linked to the respective alarm event. A camera is always assigned to an alarm zone.
The HTTP command for retrieving the image data can be found in the documentation of the camera
manufacturer.
I/O Modules
The AlarmManager-PRO can be expanded with additional modules (KIO7017, KIO7052, KIO7053) with
additional digital inputs and outputs.
This makes it possible to have external alarms for monitoring e.g. air conditioning or extinguishing systems and
UPS or other alarm systems.