9.5.3. Online wall reader
The commissioning of a Kentix online wall reader consists of 2 steps:
The wiring and the installation into the flush-mounted socket at the wall.
Two modes are available for the wiring and control of external components (factory doors, barriers):
1. Wiring of the relay directly at the wall reader (applications with low safety requirements)
2. Wiring of up to two relays at the AccessPoint (AccessPoint installed in the secure area, application with high
security requirements)
The wiring for the desired operating mode is described in the following:
9.5.3.1.
Commissioning with wiring of the relay at the wall reader
Power supply and the relay are connected directly to the wall reader. Please follow the PIN assignment as
shown on the diagram below.
9.5.3.2.
Commissioning with wiring of the relays via the AccessPoint
The voltage supply is realized as described above. In addition one of the two relays at the AccessPoint is used.
For the connection an external adapter (KIO3) is available. This is connected to the system jack of the
AccessPoint using a patch cable.
Page
(07-2018, subject to change)
kentix.com
61
Terminal connector (back of reader unit):
1 - Voltage supply 8-40 VDC (polarity: any)
2 - Voltage supply 8-40 VDC (polarity: any)
9 - Switching relay max. 30 V AC/DC, max. 1,5A (polarity: any)
10 - Switching relay max. 30 V AC/DC, max. 1,5A (polarity: any)