MULTICAL® 803
Kamstrup A/S · Technical description · 5512-2360_A1_GB_02.2019
99
Application no. 7
Open system with 2 flow meters
Inlet energy: E4 = V1 (t1-t3)k
t1
Outlet energy: E5 = V2 (t2-t3)k
t2
dE(ΔE) = E4
-E5 can be calculated by the meter.
Heat energy: E2 = V2 (t1-t2)k
t2
t3 is measured or programmed
Mass: M1 = V1 (Kmass t1)
Mass: M2 = V2 (Kmass t2)
Config. A = 3 (inlet)
Application no. 8
Hot water boiler with circulation
Tap water energy: E1 = V1 (t1-t2)k
t2
Circulated energy: E7 = V2 (t1-t3)k
t3
Mass: M1 = V1 (Kmass t1)
Mass: M3 = V2 (Kmass t3)
LV: Domestic hot water
LVK: Heat circulation
KV: Cold water
Config. A = 4 (outlet)