The below table lists the tariff types for which MULTICAL
803 can be configured and shows the tariff types available
for each meter type.
EE=00 No active tariff
If no tariff function is required, you select the setup EE=00.
However, the tariff function can, at a later stage, be activated through reconfiguration via METERTOOL HCW. See the
technical description of METERTOOL HCW (5512-2097).
EE=11 Power-controlled tariff
If the current power (P) exceeds TL2, but is lower than or equal to TL3, energy is counted in TA2 parallel to the main
register. If the current power exceeds TL3, but is lower than or equal to TL4, energy is counted in TA3 parallel to the
main register. If the current power exceeds TL4, energy is counted in TA4 parallel to the main register.
P
≤
TL2
Accumulation in main register only
TL4
>
TL3
>
TL2
TL3
≥
P
>
TL2
Accumulation in TA2 and main register
TL4
≥
P
>
TL3
Accumulation in TA3 and main register
P
>
TL4
Accumulation in TA4 and main register
Setting up data, TL3 must be higher than TL2 and TL4 must be higher than TL3.
The power-controlled tariff is e.g. used as a basis for the individual heat consumer’s connection fee. Furthermore,
this tariff type can provide valuable statistical data if the heating plant considers new construction activities.
EE= Tariff type
Function
H
ea
t me
te
r
M
et
er t
yp
e 2
H
ea
t/
co
ol
in
g m
et
er
M
et
er t
yp
e 3
H
ea
t me
te
r
M
et
er t
yp
e 4
Co
ol
in
g m
et
er
M
et
er t
yp
e 5
H
ea
t/
co
ol
in
g m
et
er
M
et
er t
yp
e 6
Vo
lu
m
e m
et
er
M
et
er t
yp
e 7
00
No active tariff
No function
•
•
•
•
•
•
11
Power tariff
Energy is accumulated in TA2, TA3 and TA4 on the basis of the
power limits entered in TL2, TL3 and TL4
•
•
•
12
Flow tariff
Energy is accumulated in TA2, TA3 and TA4 on the basis of the flow
limits entered in TL2, TL3 and TL4
•
•
•
13
t1-t2 tariff
Energy is accumulated in TA2, TA3 and TA4 on the basis of the
∆
t-
limits entered in TL2, TL3 and TL4
•
•
•
14
Inlet temperature tariff
Energy is accumulated in TA2, TA3 and TA4 on the basis of t1 limits
entered in TL2, TL3 and TL4.
•
•
•
15
Outlet temperature tariff
Energy is accumulated in TA2, TA3 and TA4 on the basis of t2 limits
entered in TL2, TL3 and TL4.
•
•
•
19
Time-controlled tariff
TL2=Start time of TA2
TL3=Start time of TA3
TL4=Start time of TA4
•
•
•
20
Heat/cooling volume tariff
(TL2, TL3 and TL4 are not
used)
Volume (V1) is divided into TA2 for heat (t1
>
t2) and TA3 for
cooling (t1
<
t2). For heat/cooling meters of meter types 3 and 6,
the energy accumulation also depends on Θ
HC
(TA4 is not used in
this tariff type).
•
•
•
21
PQ tariff
Energy is accumulated in TA2 if P
>
TL2 and in TA3 if Q
>
TL3
•
•
•