MULTICAL® 803
Kamstrup A/S · Technical description · 5512-2360_A1_GB_02.2019
91
24. Preset t5
The temperature value t5 can be adjusted in the interval 0.01...185.00 °C in the SETUP loop. This value is used in
connection with the calculation of outlet energy registers, i.e. registers A1 (A-, heat at a discount) and A2 (A+, heat
with an addition). Read more about this calculation and function in paragraph 7.1.3.
25. EndSetup
The menu item “EndSetup” enables the technician to lock the access to the SETUP loop in transport state and thus
lock the calculator against further configuration. In order to do so, the user must keep the primary key activated for
five seconds. During the five seconds, the frames around the reading EndSetup will be shown in the calculator’s
display. This action can be undone by releasing the primary key before the whole frame has been shown, i.e. before
the five seconds have passed.
“EndSetup” is an important function when the calculator is in transport state.If the calculator is in operation,
“EndSetup” is just one of three ways to exit the SETUP loop. See paragraph 6.4.