MULTICAL® 803
90
Kamstrup A/S · Technical description · 5512-2360_A1_
GB
_02.2019
If a module is not installed in the calculator or if the mounted module is not a radio module, both symbols are turned
off in the calculator’s other loops, independently of the setting of the radio on/off in the SETUP loop. MULTICAL®
803 always allows radio communication during operation.
Radio ON
Radio OFF
No module / not radio module
SETUP
loop
USER/TECH
loop
17. + 18. Inputs A1 and B1 (presetting of registers)
It is possible to preset the values of the pulse inputs A1 and B1 in the SETUP loop so that the calculator’s display is in
accordance with the connected water and/or electricity meters. The example is based on the connection of a water
meter.
Note: If the pulse inputs A2 and B2 are to be used, METERTOOL HCW is used for presetting the registers.
19. + 20. Meter numbers of inputs A1 and B1
Meter numbers of the water and/or electricity meters connected to the pulse inputs A1 and B1 can be adjusted in
the SETUP loop. In the example shown, the meter number is connected to pulse input B1.
Note: If the pulse inputs A2 and B2 are to be used, METERTOOL HCW is used for setting the meter numbers.
21. + 22. + 23. Tariff limits (TL2, TL3 and TL4)
The calculator’s three tariff limits can be adjusted in the SETUP loop. The tariff limits are only active if a tariff type
has been selected during configuration of the calculator, i.e. the EE code differs from “00”. The EE code is shown in
the TECH loop, see paragraph 6.2. If a tariff type has been selected, the menu items reflect this by displaying the
correct tariff limit units. If no tariff type has been selected, the menu items will be without units. Read more about
tariff types in paragraph 3.4.5.
Note:
It is
not
possible to have different types of tariff limits. The display readings
shown are just examples.