MULTICAL® 803
24
Kamstrup A/S · Technical description · 5512-2360_A1_
GB
_02.2019
RR - T - VVVV
Data logger profile
See paragraph 3.4.12
RR
Encryption level
Common key
2
Individual key
3
Customer label
See paragraph 3.4.14
VVVV
3.4.1
Flow sensor position >A<
Code A indicates installation of flow sensor in inlet or outlet. As the density and heat capacity of water vary with
temperature, the calculator must correct this based on the installation position (A code). Incorrect programming or
installation leads to error of measuring. See paragraph 4.3 for further details on the installation of the flow sensor in
inlet and outlet as far as heat and cooling installations are concerned.
Flow sensor position
A code
Inlet
3
Outlet
4
3.4.2
Measuring unit >B<
The B code indicates the measuring unit used in the energy register. The options are GJ, kWh, MWh or Gcal.
Measuring unit
B code
GJ
2
kWh
3
MWh
4
Gcal
1
5
1
Note that Gcal is not an SI unit. Read more about how Gcal is supported by M-Bus or wM-Bus in paragraph 11.